Vulnerability Details :

CVE-2018-7246

Summary
Assigner-schneider
Assigner Org ID-076d1eb6-cfab-4401-b34d-6dfc2a413bdb
Published At-18 Apr, 2018 | 20:00
Updated At-05 Aug, 2024 | 06:24
Rejected At-
Credits

A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext

Vendors
-
Not available
Products
-
Metrics (CVSS)
VersionBase scoreBase severityVector
Weaknesses
Attack Patterns
Solution/Workaround
References
HyperlinkResource Type
EPSS History
Score
Latest Score
-
N/A
No data available for selected date range
Percentile
Latest Percentile
-
N/A
No data available for selected date range
Stakeholder-Specific Vulnerability Categorization (SSVC)
▼Common Vulnerabilities and Exposures (CVE)
cve.org
Assigner:schneider
Assigner Org ID:076d1eb6-cfab-4401-b34d-6dfc2a413bdb
Published At:18 Apr, 2018 | 20:00
Updated At:05 Aug, 2024 | 06:24
Rejected At:
▼CVE Numbering Authority (CNA)

A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext

Affected Products
Vendor
Schneider Electric SESchneider Electric SE
Product
66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS
Versions
Affected
  • MGE Network Management Card Transverse, part number: SF66074. All card versions affected, when installed in following products: MGE Galaxy 5000, MGE Galaxy 6000, MGE Galaxy 9000, MGE EPS 7000, MGE EPS 8000, MGE EPS 6000, MGE Comet UPS, MGE Galaxy PW, MGE Galaxy 3000, MGE Galaxy 4000
Problem Types
TypeCWE IDDescription
textN/ACleartext Transmission of Sensitive Information
Type: text
CWE ID: N/A
Description: Cleartext Transmission of Sensitive Information
Metrics
VersionBase scoreBase severityVector
Metrics Other Info
Impacts
CAPEC IDDescription
Solutions

Configurations

Workarounds

Exploits

Credits

Timeline
EventDate
Replaced By

Rejected Reason

References
HyperlinkResource
https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/
x_refsource_CONFIRM
Hyperlink: https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/
Resource:
x_refsource_CONFIRM
▼Authorized Data Publishers (ADP)
CVE Program Container
Affected Products
Metrics
VersionBase scoreBase severityVector
Metrics Other Info
Impacts
CAPEC IDDescription
Solutions

Configurations

Workarounds

Exploits

Credits

Timeline
EventDate
Replaced By

Rejected Reason

References
HyperlinkResource
https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/
x_refsource_CONFIRM
x_transferred
Hyperlink: https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/
Resource:
x_refsource_CONFIRM
x_transferred
Information is not available yet
▼National Vulnerability Database (NVD)
nvd.nist.gov
Source:cybersecurity@se.com
Published At:18 Apr, 2018 | 20:29
Updated At:03 Oct, 2019 | 00:03

A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext

CISA Catalog
Date AddedDue DateVulnerability NameRequired Action
N/A
Date Added: N/A
Due Date: N/A
Vulnerability Name: N/A
Required Action: N/A
Metrics
TypeVersionBase scoreBase severityVector
Primary3.09.8CRITICAL
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Primary2.05.0MEDIUM
AV:N/AC:L/Au:N/C:P/I:N/A:N
Type: Primary
Version: 3.0
Base score: 9.8
Base severity: CRITICAL
Vector:
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Type: Primary
Version: 2.0
Base score: 5.0
Base severity: MEDIUM
Vector:
AV:N/AC:L/Au:N/C:P/I:N/A:N
CPE Matches

Schneider Electric SE
schneider-electric
>>66074_mge_network_management_card_transverse>>-
cpe:2.3:h:schneider-electric:66074_mge_network_management_card_transverse:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_comet_ups>>-
cpe:2.3:h:schneider-electric:mge_comet_ups:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_eps_6000>>-
cpe:2.3:h:schneider-electric:mge_eps_6000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_eps_7000>>-
cpe:2.3:h:schneider-electric:mge_eps_7000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_eps_8000>>-
cpe:2.3:h:schneider-electric:mge_eps_8000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_galaxy_3000>>-
cpe:2.3:h:schneider-electric:mge_galaxy_3000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_galaxy_4000>>-
cpe:2.3:h:schneider-electric:mge_galaxy_4000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_galaxy_5000>>-
cpe:2.3:h:schneider-electric:mge_galaxy_5000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_galaxy_6000>>-
cpe:2.3:h:schneider-electric:mge_galaxy_6000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_galaxy_9000>>-
cpe:2.3:h:schneider-electric:mge_galaxy_9000:-:*:*:*:*:*:*:*
Schneider Electric SE
schneider-electric
>>mge_galaxy_pw>>-
cpe:2.3:h:schneider-electric:mge_galaxy_pw:-:*:*:*:*:*:*:*
Weaknesses
CWE IDTypeSource
CWE-319Primarynvd@nist.gov
CWE ID: CWE-319
Type: Primary
Source: nvd@nist.gov
Evaluator Description

Evaluator Impact

Evaluator Solution

Vendor Statements

References
HyperlinkSourceResource
https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/cybersecurity@se.com
Mitigation
Vendor Advisory
Hyperlink: https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/
Source: cybersecurity@se.com
Resource:
Mitigation
Vendor Advisory

Change History

0
Information is not available yet

Similar CVEs

251Records found

CVE-2020-7488
Matching Score-10
Assigner-Schneider Electric
ShareView Details
Matching Score-10
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.19% / 40.81%
||
7 Day CHG~0.00%
Published-22 Apr, 2020 | 18:51
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists which could leak sensitive information transmitted between the software and the Modicon M218, M241, M251, and M258 controllers.

Action-Not Available
Vendor-n/a
Product-modicon_m241_firmwaremodicon_m218ecostruxure_machine_expertsomachine_motionmodicon_m218_firmwaremodicon_m241somachinemodicon_m258modicon_m258_firmwaremodicon_m251_firmwaremodicon_m251EcoStruxure Machine Expert (all versions)SoMachine, SoMachine Motion (all versions)Modicon M218 Logic Controller (all versions)Modicon M241 Logic Controller (all versions)Modicon M251 Logic Controller (all versions)Modicon M258 Logic Controller (all versions)
CWE ID-CWE-319
Cleartext Transmission of Sensitive Information
CVE-2021-22703
Matching Score-10
Assigner-Schneider Electric
ShareView Details
Matching Score-10
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.16% / 37.32%
||
7 Day CHG~0.00%
Published-19 Feb, 2021 | 15:14
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-319: Cleartext transmission of sensitive information vulnerability exists in PowerLogic ION7400, ION7650, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions), that could cause disclosure of user credentials when a malicious actor intercepts HTTP network traffic between a user and the device.

Action-Not Available
Vendor-n/a
Product-powerlogic_ion8650powerlogic_ion8400_firmwarepowerlogic_pm8000_firmwarepowerlogic_pm8000powerlogic_ion8300_firmwarepowerlogic_ion7400_firmwarepowerlogic_ion7650_firmwarepowerlogic_ion8800powerlogic_ion8600powerlogic_ion8500_firmwarepowerlogic_ion8300powerlogic_ion8500powerlogic_ion8600_firmwarepowerlogic_ion9000_firmwarepowerlogic_ion9000powerlogic_ion8400powerlogic_ion8800_firmwarepowerlogic_ion7400powerlogic_ion7650powerlogic_ion8650_firmwarePowerLogic ION7400, ION7650, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions)
CWE ID-CWE-319
Cleartext Transmission of Sensitive Information
CVE-2021-22702
Matching Score-10
Assigner-Schneider Electric
ShareView Details
Matching Score-10
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.14% / 35.16%
||
7 Day CHG~0.00%
Published-19 Feb, 2021 | 15:13
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-319: Cleartext transmission of sensitive information vulnerability exists in PowerLogic ION7400, ION7650, ION7700/73xx, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions), that could cause disclosure of user credentials when a malicious actor intercepts Telnet network traffic between a user and the device.

Action-Not Available
Vendor-n/a
Product-powerlogic_ion8650powerlogic_ion7700_firmwarepowerlogic_ion8400_firmwarepowerlogic_pm8000_firmwarepowerlogic_pm8000powerlogic_ion8300_firmwarepowerlogic_ion7400_firmwarepowerlogic_ion7650_firmwarepowerlogic_ion7700powerlogic_ion8600powerlogic_ion8800powerlogic_ion8500_firmwarepowerlogic_ion8600_firmwarepowerlogic_ion8500powerlogic_ion8300powerlogic_ion9000_firmwarepowerlogic_ion7300_firmwarepowerlogic_ion9000powerlogic_ion8400powerlogic_ion7300powerlogic_ion8800_firmwarepowerlogic_ion7400powerlogic_ion7650powerlogic_ion8650_firmwarePowerLogic ION7400, ION7650, ION7700/73xx, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions)
CWE ID-CWE-319
Cleartext Transmission of Sensitive Information
CVE-2020-7483
Matching Score-10
Assigner-Schneider Electric
ShareView Details
Matching Score-10
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.09% / 26.62%
||
7 Day CHG~0.00%
Published-15 Apr, 2020 | 21:03
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

**VERSION NOT SUPPORTED WHEN ASSIGNED** A vulnerability could cause certain data to be visible on the network when the 'password' feature is enabled. This vulnerability was discovered in and remediated in versions v4.9.1 and v4.10.1 on May 30, 2013. The 'password' feature is an additional optional check performed by TS1131 that it is connected to a specific controller. This data is sent as clear text and is visible on the network. This feature is not present in TriStation 1131 versions v4.9.1 and v4.10.1 through current. Therefore, the vulnerability is not present in these versions.

Action-Not Available
Vendor-n/aMicrosoft Corporation
Product-windows_7windows_xpwindows_nttristation_1131TriStation TS1131 (v4.0.0 to v4.9.0, v4.10.0)
CWE ID-CWE-319
Cleartext Transmission of Sensitive Information
CVE-2019-6845
Matching Score-10
Assigner-Schneider Electric
ShareView Details
Matching Score-10
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.21% / 42.75%
||
7 Day CHG~0.00%
Published-29 Oct, 2019 | 14:49
Updated-04 Aug, 2024 | 20:31
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists in Modicon M580, Modicon M340, Modicon Premium , Modicon Quantum (all firmware versions), which could cause the disclosure of information when transferring applications to the controller using Modbus TCP protocol.

Action-Not Available
Vendor-n/a
Product-tsxmrpc001m_firmwaretsxmrpc002m_firmwaretsxmrpp384ktsxmfpp002m_firmwaremodicon_m580_firmwaretsxmrpc448k_firmwaretsxmrpf008mtsxmrpp384k_firmwaretsxmcpc002m_firmwaretsxmrpf004mtsxmrpc768ktsxmrpc01m7tsxmrpp224kmodicon_m580tsxmrpc01m7_firmwaretsxmfp064p2tsxmrpc003m_firmwaretsxmrpc001mtsxmfpp224ktsxmrpc002mtsxmfpp004mtsxmfpp001m_firmwaretsxmrpc768k_firmwaretsxmfpp001mtsxmrpp224k_firmwaretsxmrpc007m_firmwaretsxmfpp512k_firmwaretsxmfpp224k_firmwaretsxmfp0128p2tsxmrpc007mtsxmcpc002mmodicon_m340tsxmfpp384ktsxmrpf008m_firmwaretsxmcpc512ktsxmfp0128p2_firmwaretsxmcpc512k_firmwaretsxmfpp512ktsxmrpf004m_firmwaretsxmfp064p2_firmwaretsxmrpc003mtsxmfpp002mtsxmfpp384k_firmwaretsxmrpc448ktsxmfpp004m_firmwaremodicon_m340_firmwareModicon M580, Modicon M340, Modicon Premium , Modicon Quantum (all firmware versions)
CWE ID-CWE-319
Cleartext Transmission of Sensitive Information
CVE-2022-24316
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.32% / 54.66%
||
7 Day CHG~0.00%
Published-09 Feb, 2022 | 22:05
Updated-03 Aug, 2024 | 04:07
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-665: Improper Initialization vulnerability exists that could cause information exposure when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)

Action-Not Available
Vendor-n/a
Product-interactive_graphical_scada_system_data_serverInteractive Graphical SCADA System Data Server (V15.0.0.22020 and prior)
CWE ID-CWE-665
Improper Initialization
CVE-2022-24318
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.10% / 28.35%
||
7 Day CHG~0.00%
Published-09 Feb, 2022 | 22:05
Updated-03 Aug, 2024 | 04:07
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-326: Inadequate Encryption Strength vulnerability exists that could cause non-encrypted communication with the server when outdated versions of the ViewX client are used. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions)

Action-Not Available
Vendor-n/a
Product-clearscadaecostruxure_geo_scada_expert_2020ecostruxure_geo_scada_expert_2019ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions)
CWE ID-CWE-326
Inadequate Encryption Strength
CVE-2022-24317
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.28% / 50.64%
||
7 Day CHG~0.00%
Published-09 Feb, 2022 | 22:05
Updated-03 Aug, 2024 | 04:07
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-862: Missing Authorization vulnerability exists that could cause information exposure when an attacker sends a specific message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)

Action-Not Available
Vendor-n/a
Product-interactive_graphical_scada_system_data_serverInteractive Graphical SCADA System Data Server (V15.0.0.22020 and prior)
CWE ID-CWE-862
Missing Authorization
CVE-2022-22810
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-9.8||CRITICAL
EPSS-0.30% / 52.94%
||
7 Day CHG~0.00%
Published-09 Feb, 2022 | 22:05
Updated-03 Aug, 2024 | 03:21
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow an attacker to manipulate the admin after numerous attempts at guessing credentials. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior)

Action-Not Available
Vendor-n/a
Product-fellerlynkwiser_for_knxspacelynkwiser_for_knx_firmwarefellerlynk_firmwarespacelynk_firmwarespaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior)
CWE ID-CWE-307
Improper Restriction of Excessive Authentication Attempts
CVE-2014-5412
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-5||MEDIUM
EPSS-0.53% / 66.37%
||
7 Day CHG~0.00%
Published-18 Sep, 2014 | 10:00
Updated-12 Apr, 2025 | 10:46
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allows remote attackers to read database records by leveraging access to the guest account.

Action-Not Available
Vendor-n/aSchneider Electric SEAVEVA
Product-clearscadascada_expert_clearscadan/a
CVE-2017-14024
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-9.8||CRITICAL
EPSS-3.53% / 87.18%
||
7 Day CHG~0.00%
Published-13 Nov, 2017 | 20:00
Updated-20 Apr, 2025 | 01:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-wonderware_intouchwonderware_indusoft_web_studioSchneider Electric InduSoft Web Studio and InTouch Machine Edition
CWE ID-CWE-119
Improper Restriction of Operations within the Bounds of a Memory Buffer
CVE-2020-7513
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.15% / 36.25%
||
7 Day CHG~0.00%
Published-16 Jun, 2020 | 19:45
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-312: Cleartext Storage of Sensitive Information vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to intercept traffic and read configuration data.

Action-Not Available
Vendor-n/a
Product-easergy_t300easergy_t300_firmwareEasergy T300 (Firmware version 1.5.2 and older)
CWE ID-CWE-312
Cleartext Storage of Sensitive Information
CVE-2017-13997
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-9.8||CRITICAL
EPSS-1.59% / 80.88%
||
7 Day CHG~0.00%
Published-02 Oct, 2017 | 05:00
Updated-20 Apr, 2025 | 01:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-wonderware_intouchwonderware_indusoft_web_studioSchneider Electric InduSoft Web Studio, InTouch Machine Edition
CWE ID-CWE-306
Missing Authentication for Critical Function
CVE-2016-5815
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-9.8||CRITICAL
EPSS-1.19% / 77.93%
||
7 Day CHG~0.00%
Published-13 Feb, 2017 | 21:00
Updated-20 Apr, 2025 | 01:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-ion7300ion7600ion7500ion5000ion8650ion8800Schneider Electric IONXXXX Series Power Meter Vulnerabilities
CWE ID-CWE-284
Improper Access Control
CVE-2016-4520
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-9.8||CRITICAL
EPSS-2.71% / 85.35%
||
7 Day CHG~0.00%
Published-15 Jul, 2016 | 16:00
Updated-12 Apr, 2025 | 10:46
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-pelco_digital_sentry_video_management_system_firmwaren/a
CVE-2015-3962
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-5||MEDIUM
EPSS-0.42% / 61.28%
||
7 Day CHG~0.00%
Published-18 Sep, 2015 | 22:00
Updated-12 Apr, 2025 | 10:46
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Schneider Electric StruxureWare Building Expert MPM before 2.15 does not use encryption for the client-server data stream, which allows remote attackers to discover credentials by sniffing the network.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-struxureware_building_expert_multi-purpose_managementn/a
CWE ID-CWE-522
Insufficiently Protected Credentials
CVE-2015-0997
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-5||MEDIUM
EPSS-0.60% / 68.52%
||
7 Day CHG~0.00%
Published-29 Mar, 2015 | 10:00
Updated-12 Apr, 2025 | 10:46
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 provide an HMI user interface that lists all valid usernames, which makes it easier for remote attackers to obtain access via a brute-force password-guessing attack.

Action-Not Available
Vendor-n/aSchneider Electric SEAVEVA
Product-wonderware_intouch_2014aveva_edgen/a
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2022-30235
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-8.6||HIGH
EPSS-0.34% / 55.82%
||
7 Day CHG~0.00%
Published-02 Jun, 2022 | 22:45
Updated-16 Sep, 2024 | 17:59
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow unauthorized access when an attacker uses brute force. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior)

Action-Not Available
Vendor-
Product-wiser_smart_eer21000wiser_smart_eer21001_firmwarewiser_smart_eer21000_firmwarewiser_smart_eer21001Wiser Smart
CWE ID-CWE-307
Improper Restriction of Excessive Authentication Attempts
CVE-2021-22804
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.49% / 64.57%
||
7 Day CHG~0.00%
Published-11 Feb, 2022 | 17:40
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause disclosure of arbitrary files being read in the context of the user running IGSS, due to missing validation of user supplied data in network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)

Action-Not Available
Vendor-n/a
Product-interactive_graphical_scada_system_data_collectorInteractive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)
CWE ID-CWE-22
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
CVE-2021-22798
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.29% / 52.07%
||
7 Day CHG~0.00%
Published-11 Feb, 2022 | 17:40
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause Sensitive data such as login credentials being exposed when a Network is sniffed. Affected Product: Conext� ComBox (All Versions)

Action-Not Available
Vendor-n/a
Product-conext_comboxconext_combox_firmwareConext� ComBox (All Versions)
CWE ID-CWE-522
Insufficiently Protected Credentials
CVE-2021-22806
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.39% / 58.88%
||
7 Day CHG~0.00%
Published-11 Feb, 2022 | 17:40
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-669: Incorrect Resource Transfer Between Spheres vulnerability exists that could cause data exfiltration and unauthorized access when accessing a malicious website. Affected Product: spaceLYnk (V2.6.1 and prior), Wiser for KNX (V2.6.1 and prior), fellerLYnk (V2.6.1 and prior)

Action-Not Available
Vendor-n/a
Product-fellerlynkwiser_for_knxspacelynkwiser_for_knx_firmwarefellerlynk_firmwarespacelynk_firmwarespaceLYnk (V2.6.1 and prior), Wiser for KNX (V2.6.1 and prior), fellerLYnk (V2.6.1 and prior)
CWE ID-CWE-669
Incorrect Resource Transfer Between Spheres
CVE-2021-22774
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.14% / 34.07%
||
7 Day CHG~0.00%
Published-21 Jul, 2021 | 10:45
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-759: Use of a One-Way Hash without a Salt vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could lead an attacker to get knowledge of charging station user account credentials using dictionary attacks techniques.

Action-Not Available
Vendor-n/a
Product-evlink_city_evc1s22p4evlink_parking_evf2evlink_parking_evf2_firmwareevlink_parking_ev.2_firmwareevlink_parking_evw2evlink_city_evc1s22p4_firmwareevlink_city_evc1s7p4_firmwareevlink_smart_wallbox_evb1a_firmwareevlink_smart_wallbox_evb1aevlink_parking_evw2_firmwareevlink_parking_ev.2evlink_city_evc1s7p4EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 )
CWE ID-CWE-916
Use of Password Hash With Insufficient Computational Effort
CVE-2021-22785
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.32% / 54.10%
||
7 Day CHG~0.00%
Published-11 Feb, 2022 | 17:40
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Information Exposure vulnerability exists that could cause sensitive information of files located in the web root directory to leak when an attacker sends a HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)

Action-Not Available
Vendor-n/a
Product-tsxp575634140noc78x00_firmware140noe771x1tsxety5103140cpu65150tsxp574634_firmwarebmxnoc0401_firmwaretsxp575634_firmwarebmxnoe0110_firmware140noe771x1_firmwaretsxp574634tsxp576634modicon_m340_bmxp342020bmxnoe0100_firmwaretsxety4103_firmwarebmxnoc0401tsxp576634_firmwarebmxnor0200h_rtumodicon_m340_bmxp342020_firmware140noc77101_firmwarebmxnoe0100140cpu65150_firmwarebmxnor0200h_rtu_firmwaretsxety4103140noc77101bmxnoe0110140noc78x00tsxety5103_firmwareModicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2021-22815
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-5.3||MEDIUM
EPSS-0.25% / 48.09%
||
7 Day CHG~0.00%
Published-28 Jan, 2022 | 19:09
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Information Exposure vulnerability exists which could cause the troubleshooting archive to be accessed. Affected Products: 1-Phase Uninterruptible Power Supply (UPS) using NMC2 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.8 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 250/500 (SYPX) Network Management Card 2 (NMC2): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635J (NMC2 AOS V6.9.6 and earlier), 3-Phase Uninterruptible Power Supply (UPS) using NMC2 including Symmetra PX 48/96/100/160 kW UPS (PX2), Symmetra PX 20/40 kW UPS (SY3P), Gutor (SXW, GVX), and Galaxy (GVMTS, GVMSA, GVXTS, GVXSA, G7K, GFC, G9KCHU): AP9630/AP9630CH/AP9630J, AP9631/AP9631CH/AP9631J, AP9635/AP9635CH (NMC2 AOS V6.9.6 and earlier), 1-Phase Uninterruptible Power Supply (UPS) using NMC3 including Smart-UPS, Symmetra, and Galaxy 3500 with Network Management Card 3 (NMC3): AP9640/AP9640J, AP9641/AP9641J, AP9643/AP9643J (NMC3 AOS V1.4.2.1 and earlier), APC Rack Power Distribution Units (PDU) using NMC2 2G Metered/Switched Rack PDUs with embedded NMC2: AP84XX, AP86XX, AP88XX, AP89XX (NMC2 AOS V6.9.6 and earlier), APC Rack Power Distribution Units (PDU) using NMC3 2G Metered/Switched Rack PDUs with embedded NMC3: APDU99xx (NMC3 AOS V1.4.0 and earlier), APC 3-Phase Power Distribution Products using NMC2 Galaxy RPP: GRPPIP2X84 (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) for InfraStruxure 150 kVA PDU with 84 Poles (X84P): PDPB150G6F (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for InfraStruxure 40/60kVA PDU (XPDU) PD40G6FK1-M, PD40F6FK1-M, PD40L6FK1-M, PDRPPNX10 M,PD60G6FK1, PD60F6FK1, PD60L6FK1, PDRPPNX10, PD40E5EK20-M, PD40H5EK20-M (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular 150/175kVA PDU (XRDP): PDPM150G6F, PDPM150L6F, PDPM175G6H (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for 400 and 500 kVA (PMM): PMM400-ALA, PMM400-ALAX, PMM400-CUB, PMM500-ALA, PMM500-ALAX, PMM500-CUB (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 for Modular PDU (XRDP2G): PDPM72F-5U, PDPM138H-5U, PDPM144F, PDPM138H-R, PDPM277H, PDPM288G6H (NMC2 AOS V6.9.6 and earlier), Rack Automatic Transfer Switches (ATS) Embedded NMC2: Rack Automatic Transfer Switches - AP44XX (ATS4G) (NMC2 AOS V6.9.6 and earlier), Network Management Card 2 (NMC2) Cooling Products: InRow Cooling for series ACRP5xx, ACRP1xx, ACRD5xx, and ACRC5xx SKUs (ACRP2G), InRow Cooling for series ACRC10x SKUs (RC10X2G), InRow Cooling for series ACRD6xx and ACRC6xx SKUs (ACRD2G), InRow Cooling Display for series ACRD3xx (ACRC2G), InRow Cooling for series ACSC1xx SKUs (SC2G), InRow Cooling for series ACRD1xx and ACRD2xx (ACRPTK2G), Ecoflair IAEC25/50 Air Economizer Display (EB2G), Uniflair SP UCF0481I, UCF0341I (UNFLRSP), Uniflair LE DX Perimeter Cooling Display for SKUs: IDAV, IDEV, IDWV, IUAV, IUEV, IUWV, IXAV, IXEV, IXWV, LDAV, LDEV, and LDWV (LEDX2G), Refrigerant Distribution Unit: ACDA9xx (RDU) (NMC2 AOS V6.9.6 and earlier), Environmental Monitoring Unit with embedded NMC2 (NB250): NetBotz NBRK0250 (NMC2 AOS V6.9.6 and earlier), and Network Management Card 2 (NMC2): AP9922 Battery Management System (BM4) (NMC2 AOS V6.9.6 and earlier)

Action-Not Available
Vendor-n/a
Product-single-phase_symmetragalaxy_g9kchupdpm138h-5upd60f6fk1pdpm277hpd40e5ek20-mpd40l6fk1-msymmetra_px_20galaxy_gvmsapd60g6fk1gutor_gvxgalaxy_3500network_management_card_2_firmwarepdpm150g6fpdrppnx10pdpb150g6fpmm500-alaxgutor_sxwpdpm150l6fpdpm175g6hapc_rack_power_distribution_unitspd60l6fk1pdpm288g6hnetwork_management_card_3pdpm138h-rpdrppnx10mpd40f6fk1-mrack_automatic_transfer_switchessmart-upspd40h5ek20-mnetwork_management_card_2symmetra_px_160pmm400-alaxsymmetra_px_40symmetra_px_48netbotz_nbrk0250pmm400-alagalaxy_g7xnetwork_management_card_3_firmwarepdpm144fpmm400-cubgalaxy_gfcgalaxy_rpp_grppip2x84ap9922_battery_management_systemsymmetra_px_100symmetra_px_500galaxy_gcxsagalaxy_gvxtssymmetra_px_250symmetra_px_96pmm500-cubpd40g6fk1-mgalaxy_gvmtspmm500-alapdpm72f-5un/a
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2021-22749
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-5.3||MEDIUM
EPSS-0.36% / 57.11%
||
7 Day CHG~0.00%
Published-11 Jun, 2021 | 15:40
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon X80 BMXNOR0200H RTU SV1.70 IR22 and prior that could cause information leak concerning the current RTU configuration including communication parameters dedicated to telemetry, when a specially crafted HTTP request is sent to the web server of the module.

Action-Not Available
Vendor-n/a
Product-modicon_x80_bmxnor0200h_rtu_firmwaremodicon_x80_bmxnor0200h_rtuModicon X80 BMXNOR0200H RTU SV1.70 IR22 and prior
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2021-22738
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-9.8||CRITICAL
EPSS-0.18% / 40.34%
||
7 Day CHG~0.00%
Published-26 May, 2021 | 19:19
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in homeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior that could cause unauthorized access when credentials are discovered after a brute force attack.

Action-Not Available
Vendor-n/a
Product-homelynkspacelynk_firmwarehomelynk_firmwarespacelynkhomeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior
CWE ID-CWE-327
Use of a Broken or Risky Cryptographic Algorithm
CVE-2021-22818
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.25% / 48.25%
||
7 Day CHG~0.00%
Published-28 Jan, 2022 | 19:09
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-307 Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow an attacker to gain unauthorized access to the charging station web interface by performing brute force attacks. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)

Action-Not Available
Vendor-n/a
Product-evlink_city_evc1s22p4evlink_parking_evf2evlink_parking_evp2pe_firmwareevlink_parking_evf2_firmwareevlink_parking_evw2evlink_parking_evp2peevlink_city_evc1s22p4_firmwareevlink_city_evc1s7p4_firmwareevlink_smart_wallbox_evb1a_firmwareevlink_smart_wallbox_evb1aevlink_parking_evw2_firmwareevlink_city_evc1s7p4n/a
CWE ID-CWE-307
Improper Restriction of Excessive Authentication Attempts
CVE-2021-22721
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-5.3||MEDIUM
EPSS-0.24% / 46.68%
||
7 Day CHG~0.00%
Published-21 Jul, 2021 | 10:41
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Information Exposure vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to get limited knowledge of javascript code when crafted malicious parameters are submitted to the charging station web server.

Action-Not Available
Vendor-n/a
Product-evlink_city_evc1s22p4evlink_parking_evf2evlink_parking_evf2_firmwareevlink_parking_ev.2_firmwareevlink_parking_evw2evlink_city_evc1s22p4_firmwareevlink_city_evc1s7p4_firmwareevlink_smart_wallbox_evb1a_firmwareevlink_smart_wallbox_evb1aevlink_parking_evw2_firmwareevlink_parking_ev.2evlink_city_evc1s7p4EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 )
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2021-22737
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-9.8||CRITICAL
EPSS-0.30% / 53.11%
||
7 Day CHG~0.00%
Published-26 May, 2021 | 00:00
Updated-03 Aug, 2024 | 18:51
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Insufficiently Protected Credentials vulnerability exists in homeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior that could cause unauthorized access of when credentials are discovered after a brute force attack.

Action-Not Available
Vendor-n/a
Product-homelynkspacelynk_firmwarehomelynk_firmwarespacelynkhomeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior
CWE ID-CWE-307
Improper Restriction of Excessive Authentication Attempts
CVE-2017-6034
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-9.8||CRITICAL
EPSS-0.16% / 37.79%
||
7 Day CHG~0.00%
Published-30 Jun, 2017 | 02:35
Updated-20 Apr, 2025 | 01:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

An Authentication Bypass by Capture-Replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-modbus_firmwaremodbusSchneider Electric Modicon Modbus Protocol
CWE ID-CWE-287
Improper Authentication
CWE ID-CWE-294
Authentication Bypass by Capture-replay
CVE-2018-7844
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-13.83% / 94.04%
||
7 Day CHG~0.00%
Published-22 May, 2019 | 20:06
Updated-05 Aug, 2024 | 06:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Information Exposure vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of SNMP information when reading memory blocks from the controller over Modbus.

Action-Not Available
Vendor-n/a
Product-modicon_quantummodicon_quantum_firmwaremodicon_m580_firmwaremodicon_premium_firmwaremodicon_premiummodicon_m340modicon_m340_firmwaremodicon_m580Modicon M580 Modicon M340 Modicon Quantum Modicon Premium
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2018-7787
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-5.3||MEDIUM
EPSS-0.21% / 43.29%
||
7 Day CHG~0.00%
Published-03 Jul, 2018 | 14:00
Updated-17 Sep, 2024 | 02:48
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

In Schneider Electric U.motion Builder software versions prior to v1.3.4, this vulnerability is due to improper validation of input of context parameter in HTTP GET request.

Action-Not Available
Vendor-
Product-u.motion_builderU.motion Builder
CWE ID-CWE-20
Improper Input Validation
CVE-2018-7784
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-9.8||CRITICAL
EPSS-1.00% / 76.10%
||
7 Day CHG~0.00%
Published-03 Jul, 2018 | 14:00
Updated-16 Sep, 2024 | 19:35
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

In Schneider Electric U.motion Builder software versions prior to v1.3.4, this exploit occurs when the submitted data of an input string is evaluated as a command by the application. In this way, the attacker could execute code, read the stack, or cause a segmentation fault in the running application.

Action-Not Available
Vendor-
Product-u.motionU.motion Builder
CWE ID-CWE-20
Improper Input Validation
CVE-2018-7812
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.83% / 73.66%
||
7 Day CHG~0.00%
Published-17 Dec, 2018 | 22:00
Updated-05 Aug, 2024 | 06:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

An Information Exposure through Discrepancy vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where the web server sends different responses in a way that exposes security-relevant information about the state of the product, such as whether a particular operation was successful or not.

Action-Not Available
Vendor-
Product-modicom_bmxnor0200hmodicom_quantum_firmwaremodicom_premiummodicom_bmxnor0200h_firmwaremodicom_m340_firmwaremodicom_m340modicom_quantummodicom_premium_firmwareEmbedded Web Servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2018-7845
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-4.37% / 88.52%
||
7 Day CHG~0.00%
Published-22 May, 2019 | 20:00
Updated-05 Aug, 2024 | 06:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-125: Out-of-bounds Read vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of unexpected data from the controller when reading specific memory blocks in the controller over Modbus.

Action-Not Available
Vendor-n/a
Product-modicon_quantummodicon_quantum_firmwaremodicon_m580_firmwaremodicon_premium_firmwaremodicon_premiummodicon_m340modicon_m340_firmwaremodicon_m580Modicon M580 Modicon M340 Modicon Quantum Modicon Premium
CWE ID-CWE-125
Out-of-bounds Read
CVE-2020-7519
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.28% / 50.64%
||
7 Day CHG~0.00%
Published-23 Jul, 2020 | 20:51
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-521: Weak Password Requirements vulnerability exists in Easergy Builder (Version 1.4.7.2 and older) which could allow an attacker to compromise a user account.

Action-Not Available
Vendor-n/a
Product-easergy_builderEasergy Builder (Version 1.4.7.2 and older)
CWE ID-CWE-521
Weak Password Requirements
CVE-2020-7508
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-9.8||CRITICAL
EPSS-0.26% / 48.82%
||
7 Day CHG~0.00%
Published-16 Jun, 2020 | 19:44
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-307 Improper Restriction of Excessive Authentication Attempts vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to gain full access by brute force.

Action-Not Available
Vendor-n/a
Product-easergy_t300easergy_t300_firmwareEasergy T300 (Firmware version 1.5.2 and older)
CWE ID-CWE-307
Improper Restriction of Excessive Authentication Attempts
CVE-2020-7478
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-1.85% / 82.25%
||
7 Day CHG~0.00%
Published-23 Mar, 2020 | 19:17
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-22: Improper Limitation of a Pathname to a Restricted Directory exists in IGSS (Versions 14 and prior using the service: IGSSupdate), which could allow a remote unauthenticated attacker to read arbitrary files from the IGSS server PC on an unrestricted or shared network when the IGSS Update Service is enabled.

Action-Not Available
Vendor-n/a
Product-interactive_graphical_scada_systemIGSS (Interactive Graphical SCADA System) (IGSS Version prior to 14.0.0.20009)
CWE ID-CWE-22
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
CVE-2020-7535
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.43% / 61.62%
||
7 Day CHG~0.00%
Published-11 Dec, 2020 | 00:51
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.

Action-Not Available
Vendor-n/a
Product-140noc78100140cpu65150140noc78000_firmwaretsxp575634_firmware140noc78000bmxnoe0110_firmware140cpu65160_firmwaretsxp574634modicon_m340_bmxp3420102clmodicon_m340_bmxp3420302_firmware140noc78100_firmwaremodicon_m340_bmxp342000140cpu65160modicon_m340_bmxp3420302cl_firmwaremodicon_m340_bmxp341000140noe77111_firmwaremodicon_m340_bmxp342020_firmware140noc77101_firmwaremodicon_m340_bmxp3420102_firmware140noc77101bmxnoe0110140noe77101tsxety5103_firmwaremodicon_m340_bmxp3420102cl_firmwaretsxety5103tsxp574634_firmware140noe77111modicon_m340_bmxp3420302clmodicon_m340_bmxp3420302140noe77101_firmwaremodicon_m340_bmxp342020bmxnoe0100_firmwaretsxp576634modicon_m340_bmxp341000_firmwaretsxety4103_firmwaretsxp576634_firmwaremodicon_m340_bmxp342000_firmwarebmxnoe0100140cpu65150_firmwaremodicon_m340_bmxp3420102tsxety4103tsxp575634Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions)
CWE ID-CWE-22
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
CVE-2020-7506
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.32% / 54.08%
||
7 Day CHG~0.00%
Published-16 Jun, 2020 | 19:43
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Information Exposure vulnerability exists in Easergy T300, Firmware V1.5.2 and prior, which could allow an attacker to pack or unpack the archive with the firmware for the controller and modules using the usual tar archiver resulting in an information exposure.

Action-Not Available
Vendor-n/a
Product-easergy_t300easergy_t300_firmwareEasergy T300 Firmware V1.5.2 and prior
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2020-7525
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.99% / 75.97%
||
7 Day CHG~0.00%
Published-31 Aug, 2020 | 16:12
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Improper Restriction of Excessive Authentication Attempts vulnerability exists in all hardware versions of spaceLYnk and Wiser for KNX (formerly homeLYnk) which could allow an attacker to guess a password when brute force is used.

Action-Not Available
Vendor-n/a
Product-wiser_for_knx_firmwarespacelynk_firmwarewiser_for_knxspacelynkAll hardware versions of spaceLYnk and Wiser for KNX (formerly homeLYnk)
CWE ID-CWE-307
Improper Restriction of Excessive Authentication Attempts
CVE-2020-7491
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.25% / 47.96%
||
7 Day CHG~0.00%
Published-23 Jul, 2020 | 20:46
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

**VERSION NOT SUPPORTED WHEN ASSIGNED** A legacy debug port account in TCMs installed in Tricon system versions 10.2.0 through 10.5.3 is visible on the network and could allow inappropriate access. This vulnerability was remediated in TCM version 10.5.4.

Action-Not Available
Vendor-n/a
Product-tricon_tcm_4352tristation_1131_firmwaretricon_tcm_4352atricon_tcm_4351btricon_tcm_4351a_firmwaretricon_tcm_4351_firmwaretricon_tcm_4352btricon_tcm_4352b_firmwaretristation_1131tricon_tcm_4352_firmwaretricon_tcm_4351b_firmwaretricon_tcm_4351atricon_tcm_4352a_firmwaretricon_tcm_4351Tricon system versions 10.2.0 through 10.5.3
CVE-2020-7511
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.15% / 36.25%
||
7 Day CHG~0.00%
Published-16 Jun, 2020 | 19:45
Updated-04 Aug, 2024 | 09:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to acquire a password by brute force.

Action-Not Available
Vendor-n/a
Product-easergy_t300easergy_t300_firmwareEasergy T300 (Firmware version 1.5.2 and older)
CWE ID-CWE-327
Use of a Broken or Risky Cryptographic Algorithm
CVE-2016-5818
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-9.8||CRITICAL
EPSS-0.38% / 58.53%
||
7 Day CHG~0.00%
Published-13 Feb, 2017 | 21:00
Updated-20 Apr, 2025 | 01:37
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-powerlogic_pm8eccpowerlogic_pm8ecc_firmwareSchneider Electric PowerLogic 2.651 and older
CWE ID-CWE-798
Use of Hard-coded Credentials
CVE-2020-28216
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.08% / 24.52%
||
7 Day CHG~0.00%
Published-11 Dec, 2020 | 00:51
Updated-04 Aug, 2024 | 16:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Easergy T300 (firmware 2.7 and older), that would allow an attacker to read network traffic over HTTP protocol.

Action-Not Available
Vendor-n/a
Product-easergy_t300easergy_t300_firmwareEasergy T300 (firmware 2.7 and older)
CWE ID-CWE-311
Missing Encryption of Sensitive Data
CVE-2020-28217
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.06% / 19.59%
||
7 Day CHG~0.00%
Published-11 Dec, 2020 | 00:51
Updated-04 Aug, 2024 | 16:33
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Easergy T300 (firmware 2.7 and older), that would allow an attacker to read network traffic over HTTP protocol.

Action-Not Available
Vendor-n/a
Product-easergy_t300easergy_t300_firmwareEasergy T300 (firmware 2.7 and older)
CWE ID-CWE-311
Missing Encryption of Sensitive Data
CVE-2015-6485
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Matching Score-8
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-5.3||MEDIUM
EPSS-0.42% / 60.91%
||
7 Day CHG~0.00%
Published-12 Mar, 2016 | 02:00
Updated-12 Apr, 2025 | 10:46
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Schneider Electric Telvent Sage 2300 RTUs with firmware before C3413-500-S01, and LANDAC II-2, Sage 1410, Sage 1430, Sage 1450, Sage 2400, and Sage 3030M RTUs with firmware before C3414-500-S02J2, allow remote attackers to obtain sensitive information from device memory by reading a padding field of an Ethernet packet.

Action-Not Available
Vendor-n/aSchneider Electric SE
Product-sage_landac_ii-2sage_1410sage_3030msage_2300sage_1450sage_2400sage_1430telvent_rtu_firmwaren/a
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2019-6852
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.35% / 56.59%
||
7 Day CHG~0.00%
Published-20 Nov, 2019 | 22:01
Updated-04 Aug, 2024 | 20:31
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Information Exposure vulnerability exists in Modicon Controllers (M340 CPUs, M340 communication modules, Premium CPUs, Premium communication modules, Quantum CPUs, Quantum communication modules - see security notification for specific versions), which could cause the disclosure of FTP hardcoded credentials when using the Web server of the controller on an unsecure network.

Action-Not Available
Vendor-
Product-tsx_ety_x103_firmwarebmx_noe_0100140_noc_78x00140_noe_771x1bmx_noe_0110tsx_ety_x103bmx_noc_0401_firmware140_cpu6x_firmwarebmx_p34x140_noc_78x00_firmware140_noe_771x1_firmware140_cpu6xtsx_p57xbmx_p34x_firmwarebmx_noe_0110_firmware140_noc_77101_firmwarebmx_noc_0401tsx_p57x_firmware140_noc_77101bmx_noe_0100_firmwareModicon Controllers (M340 CPUs, M340 communication modules, Premium CPUs, Premium communication modules, Quantum CPUs, Quantum communication modules - see security notification for specific versions)
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2019-6836
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.28% / 50.95%
||
7 Day CHG~0.00%
Published-17 Sep, 2019 | 19:14
Updated-04 Aug, 2024 | 20:31
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-863: Incorrect Authorization vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow the file system to access the wrong file.

Action-Not Available
Vendor-n/a
Product-meg6260-0415_firmwaremeg6260-0410meg6501-0001_firmwaremeg6501-0002meg6260-0410_firmwaremeg6501-0001meg6260-0415meg6501-0002_firmwareU.motion Servers (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, and MEG6260-0415 - U.motion KNX Server Plus, Touch 1)
CWE ID-CWE-863
Incorrect Authorization
CVE-2019-6850
Matching Score-8
Assigner-Schneider Electric
ShareView Details
Matching Score-8
Assigner-Schneider Electric
CVSS Score-7.5||HIGH
EPSS-0.32% / 54.66%
||
7 Day CHG~0.00%
Published-29 Oct, 2019 | 14:54
Updated-04 Aug, 2024 | 20:31
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

A CWE-200: Information Exposure vulnerability exists in Modicon M580, Modicon BMENOC 0311, and Modicon BMENOC 0321, which could cause the disclosure of sensitive information when reading specific registers with the REST API of the controller/communication module.

Action-Not Available
Vendor-n/a
Product-modicon_bmenoc_0321_firmwaremodicon_m580_firmwaremodicon_bmenoc_0321modicon_bmenoc_0311_firmwaremodicon_bmenoc_0311modicon_m580Modicon M580, Modicon BMENOC 0311, Modicon BMENOC 0321
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor