An issue was discovered in Mbed TLS before 2.25.0 (and before 2.16.9 LTS and before 2.7.18 LTS). The calculations performed by mbedtls_mpi_exp_mod are not limited; thus, supplying overly large parameters could lead to denial of service when generating Diffie-Hellman key pairs.
A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.
A remote cross-site request forgery (csrf) vulnerability was discovered in Aruba Operating System Software version(s): 6.x.x.x: all versions, 8.x.x.x: all versions prior to 8.8.0.0. Aruba has released patches for ArubaOS that address this security vulnerability.
A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP100 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP300 (All versions < V8.80). Specially crafted packets sent to port 4443/tcp could cause a Denial-of-Service condition.
The ULOGTOD function in ntp.d in SNTP before 4.2.7p366 does not properly perform type conversions from a precision value to a double, which allows remote attackers to cause a denial of service (infinite loop) via a crafted NTP packet.
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). When processing a DHCP ACK message, the DHCP client application does not validate the length of the Vendor option(s), leading to Denial-of-Service conditions. (FSMD-2021-0013)
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). When processing a DHCP OFFER message, the DHCP client application does not validate the length of the Vendor option(s), leading to Denial-of-Service conditions. (FSMD-2021-0008)
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4). SmartVNC has an out-of-bounds memory access vulnerability that could be triggered on the server side when sending data from the client, which could result in a Denial-of-Service condition.
In BIND 9.0.0 -> 9.11.29, 9.12.0 -> 9.16.13, and versions BIND 9.9.3-S1 -> 9.11.29-S1 and 9.16.8-S1 -> 9.16.13-S1 of BIND Supported Preview Edition, as well as release versions 9.17.0 -> 9.17.11 of the BIND 9.17 development branch, when a vulnerable version of named receives a query for a record triggering the flaw described above, the named process will terminate due to a failed assertion check. The vulnerability affects all currently maintained BIND 9 branches (9.11, 9.11-S, 9.16, 9.16-S, 9.17) as well as all other versions of BIND 9.
A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). Specially crafted PROFINET DCP packets could cause a denial of service condition of affected products.
In SQLite 3.31.1, isAuxiliaryVtabOperator allows attackers to trigger a NULL pointer dereference and segmentation fault because of generated column optimizations.
libcurl-using applications can ask for a specific client certificate to be used in a transfer. This is done with the `CURLOPT_SSLCERT` option (`--cert` with the command line tool).When libcurl is built to use the macOS native TLS library Secure Transport, an application can ask for the client certificate by name or with a file name - using the same option. If the name exists as a file, it will be used instead of by name.If the appliction runs with a current working directory that is writable by other users (like `/tmp`), a malicious user can create a file name with the same name as the app wants to use by name, and thereby trick the application to use the file based cert instead of the one referred to by name making libcurl send the wrong client certificate in the TLS connection handshake.
curl 7.21.0 to and including 7.73.0 is vulnerable to uncontrolled recursion due to a stack overflow issue in FTP wildcard match parsing.
xmlStringLenDecodeEntities in parser.c in libxml2 2.9.10 has an infinite loop in a certain end-of-file situation.
flattenSubquery in select.c in SQLite 3.30.1 mishandles certain uses of SELECT DISTINCT involving a LEFT JOIN in which the right-hand side is a view. This can cause a NULL pointer dereference (or incorrect results).
An issue was discovered in HCC Nichestack 3.0. The code that parses ICMP packets relies on an unchecked value of the IP payload size (extracted from the IP header) to compute the ICMP checksum. When the IP payload size is set to be smaller than the size of the IP header, the ICMP checksum computation function may read out of bounds, causing a Denial-of-Service.
A vulnerability has been identified in SCALANCE S602 (All versions >= V3.0 and < V4.1), SCALANCE S612 (All versions >= V3.0 and < V4.1), SCALANCE S623 (All versions >= V3.0 and < V4.1), SCALANCE S627-2M (All versions >= V3.0 and < V4.1). Specially crafted packets sent to port 443/tcp of affected devices could cause a Denial-of-Service condition of the web server.
A vulnerability has been identified in All other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions ), DIGSI 5 engineering software (All versions < V7.90), SIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.90), SIPROTEC 5 device types 7SS85 and 7KE85 (All versions < V8.01), SIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.59), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.59). Specially crafted packets sent to port 443/TCP could cause a Denial of Service condition.
A vulnerability has been identified in SIMATIC NET CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC NET CP 343-1 Lean (incl. SIPLUS variants) (All versions), SIMATIC NET CP 343-1 Standard (incl. SIPLUS variants) (All versions). Specially crafted packets sent to TCP port 102 could cause a Denial-of-Service condition on the affected devices. A cold restart might be necessary in order to recover.
Siemens SIMATIC S7-1500 CPU devices with firmware before 1.6 allow remote attackers to cause a denial of service (device restart and STOP transition) via crafted TCP packets.
A vulnerability has been identified in Teamcenter V12.4 (All versions < V12.4.0.15), Teamcenter V13.0 (All versions < V13.0.0.10), Teamcenter V13.1 (All versions < V13.1.0.10), Teamcenter V13.2 (All versions < V13.2.0.9), Teamcenter V13.3 (All versions < V13.3.0.5), Teamcenter V14.0 (All versions < V14.0.0.2). File Server Cache service in Teamcenter is vulnerable to denial of service by entering infinite loops and using up CPU cycles. This could allow an attacker to cause denial of service condition.
The package ua-parser-js before 0.7.23 are vulnerable to Regular Expression Denial of Service (ReDoS) in multiple regexes (see linked commit for more info).
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle HTTP(S) requests to the web server correctly. This could allow an attacker to exhaust system resources and create a denial of service condition for the device.
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle long file names correctly. This could allow an attacker to create a buffer overflow and create a denial of service condition for the device.
A vulnerability has been identified in SICAM PAS/PQS (All versions < V7.0), SICAM PAS/PQS (All versions >= 7.0 < V8.06). Affected software does not properly validate the input for a certain parameter in the s7ontcp.dll. This could allow an unauthenticated remote attacker to send messages and create a denial of service condition as the application crashes. At the time of assigning the CVE, the affected firmware version of the component has already been superseded by succeeding mainline versions.
A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V9.50), SIPROTEC 5 6MD85 (CP200) (All versions), SIPROTEC 5 6MD85 (CP300) (All versions < V9.50), SIPROTEC 5 6MD86 (CP200) (All versions), SIPROTEC 5 6MD86 (CP300) (All versions < V9.50), SIPROTEC 5 6MD89 (CP300) (All versions < V9.64), SIPROTEC 5 6MU85 (CP300) (All versions < V9.50), SIPROTEC 5 7KE85 (CP200) (All versions), SIPROTEC 5 7KE85 (CP300) (All versions < V9.64), SIPROTEC 5 7SA82 (CP100) (All versions), SIPROTEC 5 7SA82 (CP150) (All versions < V9.50), SIPROTEC 5 7SA84 (CP200) (All versions), SIPROTEC 5 7SA86 (CP200) (All versions), SIPROTEC 5 7SA86 (CP300) (All versions < V9.50), SIPROTEC 5 7SA87 (CP200) (All versions), SIPROTEC 5 7SA87 (CP300) (All versions < V9.50), SIPROTEC 5 7SD82 (CP100) (All versions), SIPROTEC 5 7SD82 (CP150) (All versions < V9.50), SIPROTEC 5 7SD84 (CP200) (All versions), SIPROTEC 5 7SD86 (CP200) (All versions), SIPROTEC 5 7SD86 (CP300) (All versions < V9.50), SIPROTEC 5 7SD87 (CP200) (All versions), SIPROTEC 5 7SD87 (CP300) (All versions < V9.50), SIPROTEC 5 7SJ81 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ81 (CP150) (All versions < V9.50), SIPROTEC 5 7SJ82 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ82 (CP150) (All versions < V9.50), SIPROTEC 5 7SJ85 (CP200) (All versions), SIPROTEC 5 7SJ85 (CP300) (All versions < V9.50), SIPROTEC 5 7SJ86 (CP200) (All versions), SIPROTEC 5 7SJ86 (CP300) (All versions < V9.50), SIPROTEC 5 7SK82 (CP100) (All versions < V8.89), SIPROTEC 5 7SK82 (CP150) (All versions < V9.50), SIPROTEC 5 7SK85 (CP200) (All versions), SIPROTEC 5 7SK85 (CP300) (All versions < V9.50), SIPROTEC 5 7SL82 (CP100) (All versions), SIPROTEC 5 7SL82 (CP150) (All versions < V9.50), SIPROTEC 5 7SL86 (CP200) (All versions), SIPROTEC 5 7SL86 (CP300) (All versions < V9.50), SIPROTEC 5 7SL87 (CP200) (All versions), SIPROTEC 5 7SL87 (CP300) (All versions < V9.50), SIPROTEC 5 7SS85 (CP200) (All versions), SIPROTEC 5 7SS85 (CP300) (All versions < V9.50), SIPROTEC 5 7ST85 (CP200) (All versions), SIPROTEC 5 7ST85 (CP300) (All versions < V9.64), SIPROTEC 5 7ST86 (CP300) (All versions < V9.64), SIPROTEC 5 7SX82 (CP150) (All versions < V9.50), SIPROTEC 5 7SX85 (CP300) (All versions < V9.50), SIPROTEC 5 7UM85 (CP300) (All versions < V9.50), SIPROTEC 5 7UT82 (CP100) (All versions), SIPROTEC 5 7UT82 (CP150) (All versions < V9.50), SIPROTEC 5 7UT85 (CP200) (All versions), SIPROTEC 5 7UT85 (CP300) (All versions < V9.50), SIPROTEC 5 7UT86 (CP200) (All versions), SIPROTEC 5 7UT86 (CP300) (All versions < V9.50), SIPROTEC 5 7UT87 (CP200) (All versions), SIPROTEC 5 7UT87 (CP300) (All versions < V9.50), SIPROTEC 5 7VE85 (CP300) (All versions < V9.50), SIPROTEC 5 7VK87 (CP200) (All versions), SIPROTEC 5 7VK87 (CP300) (All versions < V9.50), SIPROTEC 5 7VU85 (CP300) (All versions < V9.50), SIPROTEC 5 Communication Module ETH-BA-2EL (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BA-2EL (All versions < V9.50 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BA-2EL (All versions installed on CP200 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (All versions < V9.50 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (All versions installed on CP200 devices), SIPROTEC 5 Communication Module ETH-BD-2FO (All versions < V9.50), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V9.50). Affected devices do not properly restrict secure client-initiated renegotiations within the SSL and TLS protocols. This could allow an attacker to create a denial of service condition on the ports 443/tcp and 4443/tcp for the duration of the attack.
A vulnerability has been identified in SIMATIC S7-200 SMART CPU family (All versions >= V2.2 < V2.5.1). Affected devices do not properly handle large numbers of new incomming connections and could crash under certain circumstances. An attacker may leverage this to cause a Denial-of-Service situation.
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation which leads to a restart of the webserver of the affected product.
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.
A vulnerability has been identified in SIMATIC ET 200SP Open Controller (incl. SIPLUS variants) (V20.8), SIMATIC S7-1500 Software Controller (V20.8). The web server of the affected products contains a vulnerability that could allow a remote attacker to trigger a denial-of-service condition by sending a specially crafted HTTP request.
An issue was discovered in Contiki through 3.0. An Out-of-Bounds Read vulnerability exists in the uIP TCP/IP Stack component when calculating the checksums for IP packets in upper_layer_chksum in net/ipv4/uip.c.
libcurl versions from 7.36.0 to before 7.64.0 is vulnerable to a heap buffer out-of-bounds read. The function handling incoming NTLM type-2 messages (`lib/vauth/ntlm.c:ntlm_decode_type2_target`) does not validate incoming data correctly and is subject to an integer overflow vulnerability. Using that overflow, a malicious or broken NTLM server could trick libcurl to accept a bad length + offset combination that would lead to a buffer read out-of-bounds.
A vulnerability has been identified in SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.4.8), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.4.8). Casting an internal value could lead to floating point exception under certain circumstances. This could allow an attacker to cause a denial of service condition on affected devices.
A vulnerability has been identified in SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions < V17 Update 4), SIMATIC HMI KTP Mobile Panels (All versions < V17 Update 4), SIMATIC HMI KTP1200 Basic (All versions < V17 Update 5), SIMATIC HMI KTP400 Basic (All versions < V17 Update 5), SIMATIC HMI KTP700 Basic (All versions < V17 Update 5), SIMATIC HMI KTP900 Basic (All versions < V17 Update 5), SIPLUS HMI KTP1200 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP400 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP700 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP900 BASIC (All versions < V17 Update 5). Affected devices do not properly validate input sent to certain services over TCP. This could allow an unauthenticated remote attacker to cause a permanent denial of service condition (requiring a device reboot) by sending specially crafted TCP packets.
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), Desigo PXC00-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC00-U (All versions >= V2.3 < V6.30.37), Desigo PXC001-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC100-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC12-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC128-U (All versions >= V2.3 < V6.30.37), Desigo PXC200-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC36.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC50-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC64-U (All versions >= V2.3 < V6.30.37), Desigo PXM20-E (All versions >= V2.3 < V6.30.37), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.
A vulnerability has been identified in RUGGEDCOM i800, RUGGEDCOM i800NC, RUGGEDCOM i801, RUGGEDCOM i801NC, RUGGEDCOM i802, RUGGEDCOM i802NC, RUGGEDCOM i803, RUGGEDCOM i803NC, RUGGEDCOM M2100, RUGGEDCOM M2100F, RUGGEDCOM M2100NC, RUGGEDCOM M2200, RUGGEDCOM M2200F, RUGGEDCOM M2200NC, RUGGEDCOM M969, RUGGEDCOM M969F, RUGGEDCOM M969NC, RUGGEDCOM RMC30, RUGGEDCOM RMC30NC, RUGGEDCOM RMC8388 V4.X, RUGGEDCOM RMC8388 V5.X, RUGGEDCOM RMC8388NC V4.X, RUGGEDCOM RMC8388NC V5.X, RUGGEDCOM RP110, RUGGEDCOM RP110NC, RUGGEDCOM RS1600, RUGGEDCOM RS1600F, RUGGEDCOM RS1600FNC, RUGGEDCOM RS1600NC, RUGGEDCOM RS1600T, RUGGEDCOM RS1600TNC, RUGGEDCOM RS400, RUGGEDCOM RS400F, RUGGEDCOM RS400NC, RUGGEDCOM RS401, RUGGEDCOM RS401NC, RUGGEDCOM RS416, RUGGEDCOM RS416F, RUGGEDCOM RS416NC, RUGGEDCOM RS416NCv2 V4.X, RUGGEDCOM RS416NCv2 V5.X, RUGGEDCOM RS416P, RUGGEDCOM RS416PF, RUGGEDCOM RS416PNC, RUGGEDCOM RS416PNCv2 V4.X, RUGGEDCOM RS416PNCv2 V5.X, RUGGEDCOM RS416Pv2 V4.X, RUGGEDCOM RS416Pv2 V5.X, RUGGEDCOM RS416v2 V4.X, RUGGEDCOM RS416v2 V5.X, RUGGEDCOM RS8000, RUGGEDCOM RS8000A, RUGGEDCOM RS8000ANC, RUGGEDCOM RS8000H, RUGGEDCOM RS8000HNC, RUGGEDCOM RS8000NC, RUGGEDCOM RS8000T, RUGGEDCOM RS8000TNC, RUGGEDCOM RS900, RUGGEDCOM RS900 (32M) V4.X, RUGGEDCOM RS900 (32M) V5.X, RUGGEDCOM RS900F, RUGGEDCOM RS900G, RUGGEDCOM RS900G (32M) V4.X, RUGGEDCOM RS900G (32M) V5.X, RUGGEDCOM RS900GF, RUGGEDCOM RS900GNC, RUGGEDCOM RS900GNC(32M) V4.X, RUGGEDCOM RS900GNC(32M) V5.X, RUGGEDCOM RS900GP, RUGGEDCOM RS900GPF, RUGGEDCOM RS900GPNC, RUGGEDCOM RS900L, RUGGEDCOM RS900LNC, RUGGEDCOM RS900M-GETS-C01, RUGGEDCOM RS900M-GETS-XX, RUGGEDCOM RS900M-STND-C01, RUGGEDCOM RS900M-STND-XX, RUGGEDCOM RS900MNC-GETS-C01, RUGGEDCOM RS900MNC-GETS-XX, RUGGEDCOM RS900MNC-STND-XX, RUGGEDCOM RS900MNC-STND-XX-C01, RUGGEDCOM RS900NC, RUGGEDCOM RS900NC(32M) V4.X, RUGGEDCOM RS900NC(32M) V5.X, RUGGEDCOM RS900W, RUGGEDCOM RS910, RUGGEDCOM RS910L, RUGGEDCOM RS910LNC, RUGGEDCOM RS910NC, RUGGEDCOM RS910W, RUGGEDCOM RS920L, RUGGEDCOM RS920LNC, RUGGEDCOM RS920W, RUGGEDCOM RS930L, RUGGEDCOM RS930LNC, RUGGEDCOM RS930W, RUGGEDCOM RS940G, RUGGEDCOM RS940GF, RUGGEDCOM RS940GNC, RUGGEDCOM RS969, RUGGEDCOM RS969NC, RUGGEDCOM RSG2100, RUGGEDCOM RSG2100 (32M) V4.X, RUGGEDCOM RSG2100 (32M) V5.X, RUGGEDCOM RSG2100F, RUGGEDCOM RSG2100NC, RUGGEDCOM RSG2100NC(32M) V4.X, RUGGEDCOM RSG2100NC(32M) V5.X, RUGGEDCOM RSG2100P, RUGGEDCOM RSG2100P (32M) V4.X, RUGGEDCOM RSG2100P (32M) V5.X, RUGGEDCOM RSG2100PF, RUGGEDCOM RSG2100PNC, RUGGEDCOM RSG2100PNC (32M) V4.X, RUGGEDCOM RSG2100PNC (32M) V5.X, RUGGEDCOM RSG2200, RUGGEDCOM RSG2200F, RUGGEDCOM RSG2200NC, RUGGEDCOM RSG2288 V4.X, RUGGEDCOM RSG2288 V5.X, RUGGEDCOM RSG2288NC V4.X, RUGGEDCOM RSG2288NC V5.X, RUGGEDCOM RSG2300 V4.X, RUGGEDCOM RSG2300 V5.X, RUGGEDCOM RSG2300F, RUGGEDCOM RSG2300NC V4.X, RUGGEDCOM RSG2300NC V5.X, RUGGEDCOM RSG2300P V4.X, RUGGEDCOM RSG2300P V5.X, RUGGEDCOM RSG2300PF, RUGGEDCOM RSG2300PNC V4.X, RUGGEDCOM RSG2300PNC V5.X, RUGGEDCOM RSG2488 V4.X, RUGGEDCOM RSG2488 V5.X, RUGGEDCOM RSG2488F, RUGGEDCOM RSG2488NC V4.X, RUGGEDCOM RSG2488NC V5.X, RUGGEDCOM RSG907R, RUGGEDCOM RSG908C, RUGGEDCOM RSG909R, RUGGEDCOM RSG910C, RUGGEDCOM RSG920P V4.X, RUGGEDCOM RSG920P V5.X, RUGGEDCOM RSG920PNC V4.X, RUGGEDCOM RSG920PNC V5.X, RUGGEDCOM RSL910, RUGGEDCOM RSL910NC, RUGGEDCOM RST2228, RUGGEDCOM RST2228P, RUGGEDCOM RST916C, RUGGEDCOM RST916P. Affected devices improperly handle partial HTTP requests which makes them vulnerable to slowloris attacks. This could allow a remote attacker to create a denial of service condition that persists until the attack ends.
An issue was discovered in HCC Nichestack 3.0. The code that parses TCP packets relies on an unchecked value of the IP payload size (extracted from the IP header) to compute the length of the TCP payload within the TCP checksum computation function. When the IP payload size is set to be smaller than the size of the IP header, the TCP checksum computation function may read out of bounds (a low-impact write-out-of-bounds is also possible).
The Diffie-Hellman Key Agreement Protocol allows remote attackers (from the client side) to send arbitrary numbers that are actually not public keys, and trigger expensive server-side DHE modular-exponentiation calculations, aka a D(HE)at or D(HE)ater attack. The client needs very little CPU resources and network bandwidth. The attack may be more disruptive in cases where a client can require a server to select its largest supported key size. The basic attack scenario is that the client must claim that it can only communicate with DHE, and the server must be configured to allow DHE.
A vulnerability has been identified in RUGGEDCOM CROSSBOW (All versions < V5.5). The affected systems allow any unauthenticated client to disconnect any active user from the server. An attacker could use this vulnerability to prevent any user to perform actions in the system, causing a denial of service situation.
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SINEMA Remote Connect (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions), Totally Integrated Automation Portal (TIA Portal) V18 (All versions), Totally Integrated Automation Portal (TIA Portal) V19 (All versions), Totally Integrated Automation Portal (TIA Portal) V20 (All versions), User Management Component (UMC) (All versions < V2.15.1.1). Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions), LOGO! 12/24RCE (6ED1052-1MD08-0BA2) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA2) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA2) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA1) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA2) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA1) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA2) (All versions), LOGO! 24CEo (6ED1052-2CC08-0BA1) (All versions), LOGO! 24CEo (6ED1052-2CC08-0BA2) (All versions), LOGO! 24RCE (6ED1052-1HB08-0BA1) (All versions), LOGO! 24RCE (6ED1052-1HB08-0BA2) (All versions), LOGO! 24RCEo (6ED1052-2HB08-0BA1) (All versions), LOGO! 24RCEo (6ED1052-2HB08-0BA2) (All versions), SIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1) (All versions), SIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA2) (All versions), SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1) (All versions), SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA2) (All versions), SIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1) (All versions), SIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA2) (All versions), SIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1) (All versions), SIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA2) (All versions), SIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1) (All versions), SIPLUS LOGO! 24CE (6AG1052-1CC08-7BA2) (All versions), SIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1) (All versions), SIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA2) (All versions), SIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1) (All versions), SIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA2) (All versions), SIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1) (All versions), SIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA2) (All versions). Affected devices do not conduct certain validations when interacting with them. This could allow an unauthenticated remote attacker to manipulate the devices IP address, which means the device would not be reachable and could only be recovered by power cycling the device.
Affected devices do not properly handle the renegotiation of SSL/TLS parameters. This could allow an unauthenticated remote attacker to bypass the TCP brute force prevention and lead to a denial of service condition for the duration of the attack.
A vulnerability has been identified in Opcenter Quality V13.1 (All versions < V13.1.20220624), Opcenter Quality V13.2 (All versions < V13.2.20220624). The affected applications do not properly validate login information during authentication. This could lead to denial of service condition for existing users or allow unauthenticated remote attackers to successfully login without credentials.
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
A vulnerability has been identified in SiPass integrated (All versions < V2.95.3.18). Affected server applications contain an out of bounds read past the end of an allocated buffer while checking the integrity of incoming packets. This could allow an unauthenticated remote attacker to create a denial of service condition.
An unauthenticated remote attacker could create a permanent denial-of-service condition by sending specially crafted OSPF packets. Successful exploitation requires OSPF to be enabled on an affected device on the SCALANCE XM-400, XR-500 (All versions prior to v6.4).
SQLite through 3.31.1 allows attackers to cause a denial of service (segmentation fault) via a malformed window-function query because the AggInfo object's initialization is mishandled.
A vulnerability has been identified in SiPass integrated (All versions < V2.90.3.8). Affected server applications improperly check the size of data packets received for the configuration client login, causing a stack-based buffer overflow. This could allow an unauthenticated remote attacker to crash the server application, creating a denial of service condition.