An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code.
In Schneider Electric Pelco Sarix Professional 1st generation cameras with firmware versions prior to 3.29.69, a buffer overflow vulnerability exist in cgi program "set".
Stack-based buffer overflow in an unspecified DLL file in a DTM development kit in Schneider Electric Unity Pro, SoMachine, SoMove, SoMove Lite, Modbus Communication Library 2.2.6 and earlier, CANopen Communication Library 1.0.2 and earlier, EtherNet/IP Communication Library 1.0.0 and earlier, EM X80 Gateway DTM (MB TCP/SL), Advantys DTM for OTB, Advantys DTM for STB, KINOS DTM, SOLO DTM, and Xantrex DTMs allows remote attackers to execute arbitrary code via unspecified vectors.
A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context of a highly privileged account.
A CWE-119: Buffer Errors vulnerability exists in ProClima (all versions prior to version 8.0.0) which allows an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.
A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database.
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0.
A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files.
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.
An Authentication Bypass by Capture-Replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download.
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
CWE-787: Out-of-bounds Write vulnerability exists that could result in an authentication bypass when sending a malformed POST request and particular configuration parameters are set.
On Schneider Electric ConneXium Tofino Firewall TCSEFEA23F3F22 before 03.23, TCSEFEA23F3F20/21, and Belden Tofino Xenon Security Appliance, an SSH login can succeed with hardcoded default credentials (if the device is in the uncommissioned state).
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists in PowerLogic PM55xx, PowerLogic PM8ECC, PowerLogic EGX100 and PowerLogic EGX300 (see security notification for version infromation) that could allow an attacker administrator level access to a device.
Weak Password Recovery Mechanism for Forgotten Password vulnerability exists on Modicon Managed Switch MCSESM* and MCSESP* V8.21 and prior which could cause an unauthorized password change through HTTP / HTTPS when basic user information is known by a remote attacker.
A CWE-259: Use of Hard-coded Password vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to gain unauthorized administrative privileges when accessing to the charging station web server.
A CWE-614 Insufficient Session Expiration vulnerability exists that could allow an attacker to maintain an unauthorized access over a hijacked session to the charger station web server even after the legitimate user account holder has changed his password. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)
A CWE-434: Unrestricted Upload of File with Dangerous Type vulnerability exists that could lead to remote code execution through a number of paths, when an attacker, writes arbitrary files to folders in context of the DC module, by sending constructed messages on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)
A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T200 ((Modbus) SC2-04MOD-07000100 and earlier), Easergy T200 ((IEC104) SC2-04IEC-07000100 and earlier), and Easergy T200 ((DNP3) SC2-04DNP-07000102 and earlier) that could cause unauthorized operation when authentication is bypassed.
A CWE-798: Use of Hard-coded Credentials vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could an attacker to gain unauthorized administrative privileges when accessing to the charging station web server.
Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in homeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior that could cause unauthorized access when credentials are discovered after a brute force attack.
**VERSION NOT SUPPORTED WHEN ASSIGNED** A legacy support account in the TriStation software version v4.9.0 and earlier could cause improper access to the TriStation host machine. This was addressed in TriStation version v4.9.1 and v4.10.1 released on May 30, 2013.1
A CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exists in Andover Continuum (All versions), which could cause files on the application server filesystem to be viewable when an attacker interferes with an application's processing of XML data.
A CWE-798: Use of Hard-coded Credentials vulnerability exists in the Unity Loader and OS Loader Software (all versions). The fixed credentials are used to simplify file transfer. Today the use of fixed credentials is considered a vulnerability, which could cause unauthorized access to the file transfer service provided by the Modicon PLCs. This could result in various unintended results.
A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T300 (with firmware 2.7 and older) that could cause a wide range of problems, including information exposure, denial of service, and command execution when access to a resource from an attacker is not restricted or incorrectly restricted.
A CWE-1103: Use of Platform-Dependent Third Party Components with vulnerabilities vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to exploit the component.
A CWE-89:Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') vulnerability exists in U.motion Servers and Touch Panels (affected versions listed in the security notification) which could cause arbitrary code to be executed when a malicious command is entered.
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause tampering of files on the personal computer running C-Bus when using the File Command.
A CWE-269: Improper Privilege Management vulnerability exists that could cause a remote code execution when the transfer command is used over the network.
A CWE-502: Deserialization of untrusted data vulnerability exists that could allow an attacker to execute arbitrary code on the targeted system by sending a specifically crafted packet to the application.
CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote code execution when manipulating internal methods through Java RMI interface.
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could allow changes to administrative credentials, leading to potential remote code execution without requiring prior authentication on the Java RMI interface.
A CWE-129: Improper validation of an array index vulnerability exists where a specially crafted Ethernet request could result in denial of service or remote code execution.
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'model_name' or 'mac_address'.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'network.ieee8021x.delete_certs'.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'system.opkg.remove'.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and get the administrator privileges.
A CWE-290: Authentication Bypass by Spoofing vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause an elevation of privilege by conducting a brute force attack on Modbus parameters sent to the controller.
A CWE-501: Trust Boundary Violation vulnerability on connection to the Controller exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum and Modicon Premium which could cause unauthorized access by conducting a brute force attack on Modbus protocol to the controller.
An unrestricted Upload of File with Dangerous Type vulnerability exists on numerous methods of the IIoT Monitor 3.1.38 software that could allow upload and execution of malicious files.
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization.
A Credentials Management CWE-255 vulnerability exists in the APC UPS Network Management Card 2 AOS v6.5.6, which could cause Remote Monitoring Credentials to be viewed in plaintext when Remote Monitoring is enabled, and then disabled.
In Schneider Electric Evlink Charging Station versions prior to v3.2.0-12_v1, the Web Interface has an issue that may allow a remote attacker to gain administrative privileges without properly authenticating remote users.
A SQL Injection (CWE-89) vulnerability exists in U.motion Builder software version 1.3.4 which could cause unwanted code execution when an improper set of characters is entered.
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service or potential code execution by overwriting configuration settings of the controller over Modbus.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and gain administrator privileges because the use of hardcoded credentials.