A CWE-22: Improper Limitation of a Pathname to a Restricted Directory exists in IGSS (Versions 14 and prior using the service: IGSSupdate), which could allow a remote unauthenticated attacker to read arbitrary files from the IGSS server PC on an unrestricted or shared network when the IGSS Update Service is enabled.
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
An exposure of sensitive information vulnerability exists in Schneider Electric's Pelco VideoXpert Enterprise versions 2.0 and prior. Using a directory traversal attack, an unauthorized person can view web server files.
Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors.
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
A CWE-307 Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow an attacker to gain unauthorized access to the charging station web interface by performing brute force attacks. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)
A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions)
Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in homeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior that could cause unauthorized access when credentials are discovered after a brute force attack.
A CWE-319: Cleartext transmission of sensitive information vulnerability exists in PowerLogic ION7400, ION7650, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions), that could cause disclosure of user credentials when a malicious actor intercepts HTTP network traffic between a user and the device.
CWE-552: Files or Directories Accessible to External Parties vulnerability exists that could allow unauthenticated files and logs exfiltration and download of files when an attacker modifies the URL to download to a different location.
**VERSION NOT SUPPORTED WHEN ASSIGNED** A legacy debug port account in TCMs installed in Tricon system versions 10.2.0 through 10.5.3 is visible on the network and could allow inappropriate access. This vulnerability was remediated in TCM version 10.5.4.
Improper Restriction of Excessive Authentication Attempts vulnerability exists in all hardware versions of spaceLYnk and Wiser for KNX (formerly homeLYnk) which could allow an attacker to guess a password when brute force is used.
An information disclosure vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to obtain sensitive device information if network access was obtained.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow arbitrary system file download due to lack of validation of the shell meta characters with the value of 'system.download.sd_file'
Schneider Electric SoMachine Basic prior to v1.6 SP1 suffers from an XML External Entity (XXE) vulnerability using the DTD parameter entities technique resulting in disclosure and retrieval of arbitrary data on the affected node via out-of-band (OOB) attack. The vulnerability is triggered when input passed to the xml parser is not sanitized while parsing the xml project/template file.
An Improper Restriction of XML External Entity Reference ('XXE') vulnerability exists on numerous methods of the IIoT Monitor 3.1.38 software that could allow the software to resolve documents outside of the intended sphere of control, causing the software to embed incorrect documents into its output and expose restricted information.
A CWE-125: Out-of-bounds Read vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of unexpected data from the controller when reading specific memory blocks in the controller over Modbus.
A CWE-501: Trust Boundary Violation vulnerability on connection to the Controller exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum and Modicon Premium which could cause unauthorized access by conducting a brute force attack on Modbus protocol to the controller.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow retrieving of specially crafted URLs without authentication that can reveal sensitive information to an attacker.
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table.
A Credentials Management CWE-255 vulnerability exists in the APC UPS Network Management Card 2 AOS v6.5.6, which could cause Remote Monitoring Credentials to be viewed in plaintext when Remote Monitoring is enabled, and then disabled.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow arbitrary system file download due to lack of validation of SSL certificate.
An Information Exposure through Discrepancy vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where the web server sends different responses in a way that exposes security-relevant information about the state of the product, such as whether a particular operation was successful or not.
In Schneider Electric Wiser for KNX V2.1.0 and prior, homeLYnk V2.0.1 and prior; and spaceLYnk V2.1.0 and prior, weak and unprotected FTP access could allow an attacker unauthorized access.
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause information disclosure when specific messages are sent to the server over the database server TCP port. Affected Products: EcoStruxure Geo SCADA Expert 2019 - 2021 (formerly known as ClearSCADA) (Versions prior to October 2022)
Insufficiently Protected Credentials vulnerability exists in homeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior that could cause unauthorized access of when credentials are discovered after a brute force attack.
A CWE-200: Information Exposure vulnerability exists in Easergy T300, Firmware V1.5.2 and prior, which could allow an attacker to pack or unpack the archive with the firmware for the controller and modules using the usual tar archiver resulting in an information exposure.
**VERSION NOT SUPPORTED WHEN ASSIGNED** A vulnerability could cause certain data to be visible on the network when the 'password' feature is enabled. This vulnerability was discovered in and remediated in versions v4.9.1 and v4.10.1 on May 30, 2013. The 'password' feature is an additional optional check performed by TS1131 that it is connected to a specific controller. This data is sent as clear text and is visible on the network. This feature is not present in TriStation 1131 versions v4.9.1 and v4.10.1 through current. Therefore, the vulnerability is not present in these versions.
A CWE-307 Improper Restriction of Excessive Authentication Attempts vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to gain full access by brute force.
A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists which could leak sensitive information transmitted between the software and the Modicon M218, M241, M251, and M258 controllers.
A CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to acquire a password by brute force.
A CWE-312: Cleartext Storage of Sensitive Information vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to intercept traffic and read configuration data.
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Easergy T300 (firmware 2.7 and older), that would allow an attacker to read network traffic over HTTP protocol.
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Easergy T300 (firmware 2.7 and older), that would allow an attacker to read network traffic over HTTP protocol.
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow an attacker to manipulate the admin after numerous attempts at guessing credentials. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior)
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could cause account takeover when a brute force attack is performed on the account. Affected Products: NetBotz 4 - 355/450/455/550/570 (V4.7.0 and prior)
A CWE-787: Out-of-bounds Write vulnerability exists that could cause sensitive information leakage when accessing a malicious web page from the commissioning software. Affected Products: SoMachine HVAC (Versions prior to V2.1.0), EcoStruxure Machine Expert – HVAC (Versions prior to V1.4.0)
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists that could allow authentication credentials to be recovered when an attacker breaks the encoding. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior)
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow unauthorized access when an attacker uses brute force. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior)
Schneider Electric Telvent Sage 2300 RTUs with firmware before C3413-500-S01, and LANDAC II-2, Sage 1410, Sage 1430, Sage 1450, Sage 2400, and Sage 3030M RTUs with firmware before C3414-500-S02J2, allow remote attackers to obtain sensitive information from device memory by reading a padding field of an Ethernet packet.
Schneider Electric StruxureWare Building Expert MPM before 2.15 does not use encryption for the client-server data stream, which allows remote attackers to discover credentials by sniffing the network.
In Schneider Electric U.motion Builder software versions prior to v1.3.4, this vulnerability is due to improper validation of input of context parameter in HTTP GET request.
A CWE-807: Reliance on Untrusted Inputs in a Security Decision vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause invalid information displayed in Unity Pro software.
A CWE-200: Information Exposure vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of SNMP information when reading memory blocks from the controller over Modbus.
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks.
A CWE-200: Information Exposure vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of SNMP information when reading files from the controller over Modbus
A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext
Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allows remote attackers to read database records by leveraging access to the guest account.
A CWE-665: Improper Initialization vulnerability exists that could cause information exposure when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)