A vulnerability has been identified in RUGGEDCOM CROSSBOW (All versions < V5.5). The affected systems allow any unauthenticated client to disconnect any active user from the server. An attacker could use this vulnerability to prevent any user to perform actions in the system, causing a denial of service situation.
A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS 7 V8.1 (All versions < V8.1 Upd5), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd1), SIMATIC BATCH V7.1 and earlier (All versions), SIMATIC BATCH V8.0 (All versions < V8.0 SP1 Upd21), SIMATIC BATCH V8.1 (All versions < V8.1 SP1 Upd16), SIMATIC BATCH V8.2 (All versions < V8.2 Upd10), SIMATIC BATCH V9.0 (All versions < V9.0 SP1), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions < 15 SP1), SIMATIC PCS 7 V7.1 and earlier (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP1), SIMATIC Route Control V7.1 and earlier (All versions), SIMATIC Route Control V8.0 (All versions), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions < V9.0 Upd1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2 Upd2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1 Upd5), SIMATIC WinCC V7.2 and earlier (All versions < WinCC 7.2 Upd 15), SIMATIC WinCC V7.3 (All versions < WinCC 7.3 Upd 16), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 4), SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle HTTP(S) requests to the web server correctly. This could allow an attacker to exhaust system resources and create a denial of service condition for the device.
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread. This could allow an unauthenticated remote attacker to crash the network service.
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems improperly handles memory buffers when parsing X.509 certificates. This could allow an unauthenticated remote attacker to crash the network service.
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle long file names correctly. This could allow an attacker to create a buffer overflow and create a denial of service condition for the device.
A vulnerability has been identified in SENTRON 3KC ATC6 Expansion Module Ethernet (3KC9000-8TL75) (All versions). Affected devices expose an unused, unstable http service at port 80/tcp on the Modbus-TCP Ethernet. This could allow an attacker on the same Modbus network to create a denial of service condition that forces the device to reboot.
A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations.
A vulnerability has been identified in SCALANCE XM408-4C (All versions < V6.5), SCALANCE XM408-4C (L3 int.) (All versions < V6.5), SCALANCE XM408-8C (All versions < V6.5), SCALANCE XM408-8C (L3 int.) (All versions < V6.5), SCALANCE XM416-4C (All versions < V6.5), SCALANCE XM416-4C (L3 int.) (All versions < V6.5), SCALANCE XR524-8C, 1x230V (All versions < V6.5), SCALANCE XR524-8C, 1x230V (L3 int.) (All versions < V6.5), SCALANCE XR524-8C, 24V (All versions < V6.5), SCALANCE XR524-8C, 24V (L3 int.) (All versions < V6.5), SCALANCE XR524-8C, 2x230V (All versions < V6.5), SCALANCE XR524-8C, 2x230V (L3 int.) (All versions < V6.5), SCALANCE XR526-8C, 1x230V (All versions < V6.5), SCALANCE XR526-8C, 1x230V (L3 int.) (All versions < V6.5), SCALANCE XR526-8C, 24V (All versions < V6.5), SCALANCE XR526-8C, 24V (L3 int.) (All versions < V6.5), SCALANCE XR526-8C, 2x230V (All versions < V6.5), SCALANCE XR526-8C, 2x230V (L3 int.) (All versions < V6.5), SCALANCE XR528-6M (All versions < V6.5), SCALANCE XR528-6M (2HR2) (All versions < V6.5), SCALANCE XR528-6M (2HR2, L3 int.) (All versions < V6.5), SCALANCE XR528-6M (L3 int.) (All versions < V6.5), SCALANCE XR552-12M (All versions < V6.5), SCALANCE XR552-12M (2HR2) (All versions < V6.5), SCALANCE XR552-12M (2HR2) (All versions < V6.5), SCALANCE XR552-12M (2HR2, L3 int.) (All versions < V6.5). The OSPF protocol implementation in affected devices fails to verify the checksum and length fields in the OSPF LS Update messages. An unauthenticated remote attacker could exploit this vulnerability to cause interruptions in the network by sending specially crafted OSPF packets. Successful exploitation requires OSPF to be enabled on an affected device.
A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP100 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP300 (All versions < V8.80). Received webpackets are not properly processed. An unauthenticated remote attacker with access to any of the Ethernet interfaces could send specially crafted packets to force a restart of the target device.
A vulnerability has been identified in SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 ERPC (All versions), SIMATIC CP 343-1 Lean (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3). Sending a specially crafted packet to port 102/tcp of an affected device could cause a denial of service condition. A restart is needed to restore normal operations.
Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial of service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device.
A vulnerability has been identified in SIMATIC CP 343-1 (6GK7343-1EX30-0XE0) (All versions), SIMATIC CP 343-1 Lean (6GK7343-1CX10-0XE0) (All versions), SIPLUS NET CP 343-1 (6AG1343-1EX30-7XE0) (All versions), SIPLUS NET CP 343-1 Lean (6AG1343-1CX10-2XE0) (All versions). Affected products incorrectly validate TCP sequence numbers. This could allow an unauthenticated remote attacker to create a denial of service condition by injecting spoofed TCP RST packets.
A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.7). The affected application allows IP configuration change without authentication to the device. This could allow an attacker to cause denial of service condition.
A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). Specially crafted PROFINET DCP packets could cause a denial of service condition of affected products.
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). When processing a DHCP ACK message, the DHCP client application does not validate the length of the Vendor option(s), leading to Denial-of-Service conditions. (FSMD-2021-0013)
Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a denial of service condition. A restart is needed to restore normal operations.
A vulnerability has been identified in Opcenter Execution Foundation (All versions < V2407), Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an out of bounds write past the end of an allocated buffer when handling specific requests on port 4002/tcp. This could allow an attacker to crash the application. The corresponding service is auto-restarted after the crash.
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4), SINAMICS GH150 (All versions), SINAMICS GL150 (with option X30) (All versions), SINAMICS GM150 (with option X30) (All versions), SINAMICS SH150 (All versions), SINAMICS SL150 (All versions), SINAMICS SM120 (All versions), SINAMICS SM150 (All versions), SINAMICS SM150i (All versions). SmartVNC has a heap allocation leak vulnerability in the server Tight encoder, which could result in a Denial-of-Service condition.
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (All versions including affected IPv6 stack). The function that processes the Hop-by-Hop extension header in IPv6 packets and its options lacks any checks against the length field of the header, allowing attackers to put the function into an infinite loop by supplying arbitrary length values.
A vulnerability has been identified in RUGGEDCOM i800, RUGGEDCOM i800NC, RUGGEDCOM i801, RUGGEDCOM i801NC, RUGGEDCOM i802, RUGGEDCOM i802NC, RUGGEDCOM i803, RUGGEDCOM i803NC, RUGGEDCOM M2100, RUGGEDCOM M2100F, RUGGEDCOM M2100NC, RUGGEDCOM M2200, RUGGEDCOM M2200F, RUGGEDCOM M2200NC, RUGGEDCOM M969, RUGGEDCOM M969F, RUGGEDCOM M969NC, RUGGEDCOM RMC30, RUGGEDCOM RMC30NC, RUGGEDCOM RMC8388 V4.X, RUGGEDCOM RMC8388 V5.X, RUGGEDCOM RMC8388NC V4.X, RUGGEDCOM RMC8388NC V5.X, RUGGEDCOM RP110, RUGGEDCOM RP110NC, RUGGEDCOM RS1600, RUGGEDCOM RS1600F, RUGGEDCOM RS1600FNC, RUGGEDCOM RS1600NC, RUGGEDCOM RS1600T, RUGGEDCOM RS1600TNC, RUGGEDCOM RS400, RUGGEDCOM RS400F, RUGGEDCOM RS400NC, RUGGEDCOM RS401, RUGGEDCOM RS401NC, RUGGEDCOM RS416, RUGGEDCOM RS416F, RUGGEDCOM RS416NC, RUGGEDCOM RS416NCv2 V4.X, RUGGEDCOM RS416NCv2 V5.X, RUGGEDCOM RS416P, RUGGEDCOM RS416PF, RUGGEDCOM RS416PNC, RUGGEDCOM RS416PNCv2 V4.X, RUGGEDCOM RS416PNCv2 V5.X, RUGGEDCOM RS416Pv2 V4.X, RUGGEDCOM RS416Pv2 V5.X, RUGGEDCOM RS416v2 V4.X, RUGGEDCOM RS416v2 V5.X, RUGGEDCOM RS8000, RUGGEDCOM RS8000A, RUGGEDCOM RS8000ANC, RUGGEDCOM RS8000H, RUGGEDCOM RS8000HNC, RUGGEDCOM RS8000NC, RUGGEDCOM RS8000T, RUGGEDCOM RS8000TNC, RUGGEDCOM RS900, RUGGEDCOM RS900 (32M) V4.X, RUGGEDCOM RS900 (32M) V5.X, RUGGEDCOM RS900F, RUGGEDCOM RS900G, RUGGEDCOM RS900G (32M) V4.X, RUGGEDCOM RS900G (32M) V5.X, RUGGEDCOM RS900GF, RUGGEDCOM RS900GNC, RUGGEDCOM RS900GNC(32M) V4.X, RUGGEDCOM RS900GNC(32M) V5.X, RUGGEDCOM RS900GP, RUGGEDCOM RS900GPF, RUGGEDCOM RS900GPNC, RUGGEDCOM RS900L, RUGGEDCOM RS900LNC, RUGGEDCOM RS900M-GETS-C01, RUGGEDCOM RS900M-GETS-XX, RUGGEDCOM RS900M-STND-C01, RUGGEDCOM RS900M-STND-XX, RUGGEDCOM RS900MNC-GETS-C01, RUGGEDCOM RS900MNC-GETS-XX, RUGGEDCOM RS900MNC-STND-XX, RUGGEDCOM RS900MNC-STND-XX-C01, RUGGEDCOM RS900NC, RUGGEDCOM RS900NC(32M) V4.X, RUGGEDCOM RS900NC(32M) V5.X, RUGGEDCOM RS900W, RUGGEDCOM RS910, RUGGEDCOM RS910L, RUGGEDCOM RS910LNC, RUGGEDCOM RS910NC, RUGGEDCOM RS910W, RUGGEDCOM RS920L, RUGGEDCOM RS920LNC, RUGGEDCOM RS920W, RUGGEDCOM RS930L, RUGGEDCOM RS930LNC, RUGGEDCOM RS930W, RUGGEDCOM RS940G, RUGGEDCOM RS940GF, RUGGEDCOM RS940GNC, RUGGEDCOM RS969, RUGGEDCOM RS969NC, RUGGEDCOM RSG2100, RUGGEDCOM RSG2100 (32M) V4.X, RUGGEDCOM RSG2100 (32M) V5.X, RUGGEDCOM RSG2100F, RUGGEDCOM RSG2100NC, RUGGEDCOM RSG2100NC(32M) V4.X, RUGGEDCOM RSG2100NC(32M) V5.X, RUGGEDCOM RSG2100P, RUGGEDCOM RSG2100P (32M) V4.X, RUGGEDCOM RSG2100P (32M) V5.X, RUGGEDCOM RSG2100PF, RUGGEDCOM RSG2100PNC, RUGGEDCOM RSG2100PNC (32M) V4.X, RUGGEDCOM RSG2100PNC (32M) V5.X, RUGGEDCOM RSG2200, RUGGEDCOM RSG2200F, RUGGEDCOM RSG2200NC, RUGGEDCOM RSG2288 V4.X, RUGGEDCOM RSG2288 V5.X, RUGGEDCOM RSG2288NC V4.X, RUGGEDCOM RSG2288NC V5.X, RUGGEDCOM RSG2300 V4.X, RUGGEDCOM RSG2300 V5.X, RUGGEDCOM RSG2300F, RUGGEDCOM RSG2300NC V4.X, RUGGEDCOM RSG2300NC V5.X, RUGGEDCOM RSG2300P V4.X, RUGGEDCOM RSG2300P V5.X, RUGGEDCOM RSG2300PF, RUGGEDCOM RSG2300PNC V4.X, RUGGEDCOM RSG2300PNC V5.X, RUGGEDCOM RSG2488 V4.X, RUGGEDCOM RSG2488 V5.X, RUGGEDCOM RSG2488F, RUGGEDCOM RSG2488NC V4.X, RUGGEDCOM RSG2488NC V5.X, RUGGEDCOM RSG907R, RUGGEDCOM RSG908C, RUGGEDCOM RSG909R, RUGGEDCOM RSG910C, RUGGEDCOM RSG920P V4.X, RUGGEDCOM RSG920P V5.X, RUGGEDCOM RSG920PNC V4.X, RUGGEDCOM RSG920PNC V5.X, RUGGEDCOM RSL910, RUGGEDCOM RSL910NC, RUGGEDCOM RST2228, RUGGEDCOM RST2228P, RUGGEDCOM RST916C, RUGGEDCOM RST916P. The web server of the affected devices contains a vulnerability that may lead to a denial of service condition. An attacker may cause total loss of availability of the web server, which might recover after the attack is over.
A vulnerability has been identified in RUGGEDCOM RM1224 (V6.3), SCALANCE M-800 (V6.3), SCALANCE S615 (V6.3), SCALANCE SC-600 (All Versions >= V2.1 and < V2.1.3). Multiple failed SSH authentication attempts could trigger a temporary Denial-of-Service under certain conditions. When triggered, the device will reboot automatically.
A vulnerability has been identified in Automation License Manager 5 (All versions), Automation License Manager 6 (All versions < V6.0 SP9 Update 2). Sending specially crafted packets to port 4410/tcp of an affected system could lead to extensive memory being consumed and as such could cause a denial-of-service preventing legitimate users from using the system.
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4). SmartVNC has an out-of-bounds memory access vulnerability that could be triggered on the client side when sending data from the server, which could result in a Denial-of-Service condition.
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4). SmartVNC has an out-of-bounds memory access vulnerability that could be triggered on the server side when sending data from the client, which could result in a Denial-of-Service condition.
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SINEMA Remote Connect (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions), Totally Integrated Automation Portal (TIA Portal) V18 (All versions), Totally Integrated Automation Portal (TIA Portal) V19 (All versions), Totally Integrated Automation Portal (TIA Portal) V20 (All versions), User Management Component (UMC) (All versions < V2.15.1.1). Affected products contain a out of bound write buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (All versions including affected IPv6 stack). The function that processes IPv6 headers does not check the lengths of extension header options, allowing attackers to put this function into an infinite loop with crafted length values.
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SINEMA Remote Connect (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions), Totally Integrated Automation Portal (TIA Portal) V18 (All versions), Totally Integrated Automation Portal (TIA Portal) V19 (All versions), Totally Integrated Automation Portal (TIA Portal) V20 (All versions), User Management Component (UMC) (All versions < V2.15.1.1). Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SINEMA Remote Connect (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions), Totally Integrated Automation Portal (TIA Portal) V18 (All versions), Totally Integrated Automation Portal (TIA Portal) V19 (All versions), Totally Integrated Automation Portal (TIA Portal) V20 (All versions), User Management Component (UMC) (All versions < V2.15.1.1). Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
A vulnerability has been identified in SIMATIC MV540 H (All versions < V3.3.4), SIMATIC MV540 S (All versions < V3.3.4), SIMATIC MV550 H (All versions < V3.3.4), SIMATIC MV550 S (All versions < V3.3.4), SIMATIC MV560 U (All versions < V3.3.4), SIMATIC MV560 X (All versions < V3.3.4). Affected devices cannot properly process specially crafted Ethernet frames sent to the devices. This could allow an unauthenticated remote attacker to cause a denial of service condition. The affected devices must be restarted manually.
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation which leads to a restart of the webserver of the affected product.
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.
A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions), LOGO! 12/24RCE (6ED1052-1MD08-0BA2) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA2) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA2) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA1) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA2) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA1) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA2) (All versions), LOGO! 24CEo (6ED1052-2CC08-0BA1) (All versions), LOGO! 24CEo (6ED1052-2CC08-0BA2) (All versions), LOGO! 24RCE (6ED1052-1HB08-0BA1) (All versions), LOGO! 24RCE (6ED1052-1HB08-0BA2) (All versions), LOGO! 24RCEo (6ED1052-2HB08-0BA1) (All versions), LOGO! 24RCEo (6ED1052-2HB08-0BA2) (All versions), SIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1) (All versions), SIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA2) (All versions), SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1) (All versions), SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA2) (All versions), SIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1) (All versions), SIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA2) (All versions), SIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1) (All versions), SIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA2) (All versions), SIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1) (All versions), SIPLUS LOGO! 24CE (6AG1052-1CC08-7BA2) (All versions), SIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1) (All versions), SIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA2) (All versions), SIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1) (All versions), SIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA2) (All versions), SIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1) (All versions), SIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA2) (All versions). Affected devices do not conduct certain validations when interacting with them. This could allow an unauthenticated remote attacker to manipulate the devices IP address, which means the device would not be reachable and could only be recovered by power cycling the device.
A vulnerability has been identified in SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions < V17 Update 4), SIMATIC HMI KTP Mobile Panels (All versions < V17 Update 4), SIMATIC HMI KTP1200 Basic (All versions < V17 Update 5), SIMATIC HMI KTP400 Basic (All versions < V17 Update 5), SIMATIC HMI KTP700 Basic (All versions < V17 Update 5), SIMATIC HMI KTP900 Basic (All versions < V17 Update 5), SIPLUS HMI KTP1200 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP400 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP700 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP900 BASIC (All versions < V17 Update 5). Affected devices do not properly validate input sent to certain services over TCP. This could allow an unauthenticated remote attacker to cause a permanent denial of service condition (requiring a device reboot) by sending specially crafted TCP packets.
A vulnerability has been identified in SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.4.8), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.4.8). Casting an internal value could lead to floating point exception under certain circumstances. This could allow an attacker to cause a denial of service condition on affected devices.
A vulnerability has been identified in Opcenter Quality V13.1 (All versions < V13.1.20220624), Opcenter Quality V13.2 (All versions < V13.2.20220624). The affected applications do not properly validate login information during authentication. This could lead to denial of service condition for existing users or allow unauthenticated remote attackers to successfully login without credentials.
A vulnerability has been identified in RUGGEDCOM i800, RUGGEDCOM i800NC, RUGGEDCOM i801, RUGGEDCOM i801NC, RUGGEDCOM i802, RUGGEDCOM i802NC, RUGGEDCOM i803, RUGGEDCOM i803NC, RUGGEDCOM M2100, RUGGEDCOM M2100F, RUGGEDCOM M2100NC, RUGGEDCOM M2200, RUGGEDCOM M2200F, RUGGEDCOM M2200NC, RUGGEDCOM M969, RUGGEDCOM M969F, RUGGEDCOM M969NC, RUGGEDCOM RMC30, RUGGEDCOM RMC30NC, RUGGEDCOM RMC8388 V4.X, RUGGEDCOM RMC8388 V5.X, RUGGEDCOM RMC8388NC V4.X, RUGGEDCOM RMC8388NC V5.X, RUGGEDCOM RP110, RUGGEDCOM RP110NC, RUGGEDCOM RS1600, RUGGEDCOM RS1600F, RUGGEDCOM RS1600FNC, RUGGEDCOM RS1600NC, RUGGEDCOM RS1600T, RUGGEDCOM RS1600TNC, RUGGEDCOM RS400, RUGGEDCOM RS400F, RUGGEDCOM RS400NC, RUGGEDCOM RS401, RUGGEDCOM RS401NC, RUGGEDCOM RS416, RUGGEDCOM RS416F, RUGGEDCOM RS416NC, RUGGEDCOM RS416NCv2 V4.X, RUGGEDCOM RS416NCv2 V5.X, RUGGEDCOM RS416P, RUGGEDCOM RS416PF, RUGGEDCOM RS416PNC, RUGGEDCOM RS416PNCv2 V4.X, RUGGEDCOM RS416PNCv2 V5.X, RUGGEDCOM RS416Pv2 V4.X, RUGGEDCOM RS416Pv2 V5.X, RUGGEDCOM RS416v2 V4.X, RUGGEDCOM RS416v2 V5.X, RUGGEDCOM RS8000, RUGGEDCOM RS8000A, RUGGEDCOM RS8000ANC, RUGGEDCOM RS8000H, RUGGEDCOM RS8000HNC, RUGGEDCOM RS8000NC, RUGGEDCOM RS8000T, RUGGEDCOM RS8000TNC, RUGGEDCOM RS900, RUGGEDCOM RS900 (32M) V4.X, RUGGEDCOM RS900 (32M) V5.X, RUGGEDCOM RS900F, RUGGEDCOM RS900G, RUGGEDCOM RS900G (32M) V4.X, RUGGEDCOM RS900G (32M) V5.X, RUGGEDCOM RS900GF, RUGGEDCOM RS900GNC, RUGGEDCOM RS900GNC(32M) V4.X, RUGGEDCOM RS900GNC(32M) V5.X, RUGGEDCOM RS900GP, RUGGEDCOM RS900GPF, RUGGEDCOM RS900GPNC, RUGGEDCOM RS900L, RUGGEDCOM RS900LNC, RUGGEDCOM RS900M-GETS-C01, RUGGEDCOM RS900M-GETS-XX, RUGGEDCOM RS900M-STND-C01, RUGGEDCOM RS900M-STND-XX, RUGGEDCOM RS900MNC-GETS-C01, RUGGEDCOM RS900MNC-GETS-XX, RUGGEDCOM RS900MNC-STND-XX, RUGGEDCOM RS900MNC-STND-XX-C01, RUGGEDCOM RS900NC, RUGGEDCOM RS900NC(32M) V4.X, RUGGEDCOM RS900NC(32M) V5.X, RUGGEDCOM RS900W, RUGGEDCOM RS910, RUGGEDCOM RS910L, RUGGEDCOM RS910LNC, RUGGEDCOM RS910NC, RUGGEDCOM RS910W, RUGGEDCOM RS920L, RUGGEDCOM RS920LNC, RUGGEDCOM RS920W, RUGGEDCOM RS930L, RUGGEDCOM RS930LNC, RUGGEDCOM RS930W, RUGGEDCOM RS940G, RUGGEDCOM RS940GF, RUGGEDCOM RS940GNC, RUGGEDCOM RS969, RUGGEDCOM RS969NC, RUGGEDCOM RSG2100, RUGGEDCOM RSG2100 (32M) V4.X, RUGGEDCOM RSG2100 (32M) V5.X, RUGGEDCOM RSG2100F, RUGGEDCOM RSG2100NC, RUGGEDCOM RSG2100NC(32M) V4.X, RUGGEDCOM RSG2100NC(32M) V5.X, RUGGEDCOM RSG2100P, RUGGEDCOM RSG2100P (32M) V4.X, RUGGEDCOM RSG2100P (32M) V5.X, RUGGEDCOM RSG2100PF, RUGGEDCOM RSG2100PNC, RUGGEDCOM RSG2100PNC (32M) V4.X, RUGGEDCOM RSG2100PNC (32M) V5.X, RUGGEDCOM RSG2200, RUGGEDCOM RSG2200F, RUGGEDCOM RSG2200NC, RUGGEDCOM RSG2288 V4.X, RUGGEDCOM RSG2288 V5.X, RUGGEDCOM RSG2288NC V4.X, RUGGEDCOM RSG2288NC V5.X, RUGGEDCOM RSG2300 V4.X, RUGGEDCOM RSG2300 V5.X, RUGGEDCOM RSG2300F, RUGGEDCOM RSG2300NC V4.X, RUGGEDCOM RSG2300NC V5.X, RUGGEDCOM RSG2300P V4.X, RUGGEDCOM RSG2300P V5.X, RUGGEDCOM RSG2300PF, RUGGEDCOM RSG2300PNC V4.X, RUGGEDCOM RSG2300PNC V5.X, RUGGEDCOM RSG2488 V4.X, RUGGEDCOM RSG2488 V5.X, RUGGEDCOM RSG2488F, RUGGEDCOM RSG2488NC V4.X, RUGGEDCOM RSG2488NC V5.X, RUGGEDCOM RSG907R, RUGGEDCOM RSG908C, RUGGEDCOM RSG909R, RUGGEDCOM RSG910C, RUGGEDCOM RSG920P V4.X, RUGGEDCOM RSG920P V5.X, RUGGEDCOM RSG920PNC V4.X, RUGGEDCOM RSG920PNC V5.X, RUGGEDCOM RSL910, RUGGEDCOM RSL910NC, RUGGEDCOM RST2228, RUGGEDCOM RST2228P, RUGGEDCOM RST916C, RUGGEDCOM RST916P. Affected devices improperly handle partial HTTP requests which makes them vulnerable to slowloris attacks. This could allow a remote attacker to create a denial of service condition that persists until the attack ends.
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), Desigo PXC00-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC00-U (All versions >= V2.3 < V6.30.37), Desigo PXC001-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC100-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC12-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC128-U (All versions >= V2.3 < V6.30.37), Desigo PXC200-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC36.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC50-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC64-U (All versions >= V2.3 < V6.30.37), Desigo PXM20-E (All versions >= V2.3 < V6.30.37), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.
A vulnerability has been identified in Teamcenter V12.4 (All versions < V12.4.0.15), Teamcenter V13.0 (All versions < V13.0.0.10), Teamcenter V13.1 (All versions < V13.1.0.10), Teamcenter V13.2 (All versions < V13.2.0.9), Teamcenter V13.3 (All versions < V13.3.0.5), Teamcenter V14.0 (All versions < V14.0.0.2). File Server Cache service in Teamcenter is vulnerable to denial of service by entering infinite loops and using up CPU cycles. This could allow an attacker to cause denial of service condition.
A vulnerability has been identified in SIPROTEC 4 6MD61 (All versions), SIPROTEC 4 6MD63 (All versions), SIPROTEC 4 6MD66 (All versions), SIPROTEC 4 6MD665 (All versions), SIPROTEC 4 7SA522 (All versions), SIPROTEC 4 7SA6 (All versions < V4.78), SIPROTEC 4 7SD5 (All versions < V4.78), SIPROTEC 4 7SD610 (All versions < V4.78), SIPROTEC 4 7SJ61 (All versions), SIPROTEC 4 7SJ62 (All versions), SIPROTEC 4 7SJ63 (All versions), SIPROTEC 4 7SJ64 (All versions), SIPROTEC 4 7SJ66 (All versions), SIPROTEC 4 7SS52 (All versions), SIPROTEC 4 7ST6 (All versions), SIPROTEC 4 7UM61 (All versions), SIPROTEC 4 7UM62 (All versions), SIPROTEC 4 7UT612 (All versions), SIPROTEC 4 7UT613 (All versions), SIPROTEC 4 7UT63 (All versions), SIPROTEC 4 7VE6 (All versions), SIPROTEC 4 7VK61 (All versions), SIPROTEC 4 7VU683 (All versions), SIPROTEC 4 Compact 7RW80 (All versions), SIPROTEC 4 Compact 7SD80 (All versions), SIPROTEC 4 Compact 7SJ80 (All versions), SIPROTEC 4 Compact 7SJ81 (All versions), SIPROTEC 4 Compact 7SK80 (All versions), SIPROTEC 4 Compact 7SK81 (All versions). Affected devices do not properly handle interrupted operations of file transfer. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the devices need to be restarted.
A vulnerability has been identified in SiPass integrated (All versions < V2.90.3.8). Affected server applications improperly check the size of data packets received for the configuration client login, causing a stack-based buffer overflow. This could allow an unauthenticated remote attacker to crash the server application, creating a denial of service condition.
A vulnerability has been identified in SiPass integrated (All versions < V2.95.3.18). Affected server applications contain an out of bounds read past the end of an allocated buffer while checking the integrity of incoming packets. This could allow an unauthenticated remote attacker to create a denial of service condition.
A vulnerability has been identified in SINEC INS (All versions < V1.0 SP2 Update 3). The affected application does not properly restrict the size of generated log files. This could allow an unauthenticated remote attacker to trigger a large amount of logged events to exhaust the system's resources and create a denial of service condition.
The OPC UA implementations (ANSI C and C++) in affected products contain an integer overflow vulnerability that could cause the application to run into an infinite loop during certificate validation. This could allow an unauthenticated remote attacker to create a denial of service condition by sending a specially crafted certificate.
A vulnerability has been identified in EN100 Ethernet module DNP3 IP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.40), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint manupulating a specific argument. This could allow an attacker to crash the affected application leading to a denial of service condition
A vulnerability has been identified in SIMATIC S7-200 SMART CPU CR40 (6ES7288-1CR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU CR60 (6ES7288-1CR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA1) (All versions). Affected devices do not properly handle TCP packets with an incorrect structure. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the network cable of the device needs to be unplugged and re-plugged.
A vulnerability has been identified in EN100 Ethernet module DNP3 IP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint. This could allow an attacker to crash the affected application leading to a denial of service condition.