A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
A remote code execution security issue exists in the Rockwell Automation Arena®. A crafted DOE file can force Arena Simulation to write beyond the boundaries of an allocated object. Exploitation requires user interaction, such as opening a malicious file within the software. If exploited, a threat actor could execute arbitrary code on the target system. The software must run under the context of the administrator in order to cause worse case impact. This is reflected in the Rockwell CVSS score, as AT:P.
A remote code execution security issue exists in the Rockwell Automation Arena®. A crafted DOE file can force Arena Simulation to write beyond the boundaries of an allocated object. Exploitation requires user interaction, such as opening a malicious file within the software. If exploited, a threat actor could execute arbitrary code on the target system. The software must run under the context of the administrator in order to cause worse case impact. This is reflected in the Rockwell CVSS score, as AT:P.
A Remote Code Execution vulnerability exists in the affected product. The vulnerability requires a high level of permissions and exists due to improper input validation resulting in the possibility of a malicious Updated Agent being deployed.
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
Rockwell Automation FactoryTalk View Site Edition insufficiently validates user input, which could potentially allow threat actors to send malicious data bringing the product offline. If exploited, the product would become unavailable and require a restart to recover resulting in a denial-of-service condition.
CVE-2024-7507 IMPACT A denial-of-service vulnerability exists in the affected products. This vulnerability occurs when a malformed PCCC message is received, causing a fault in the controller.
CVE-2024-7515 IMPACT A denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller.
Due to an improper input validation, an unauthenticated threat actor can send a malicious message to a monitor thread within Rockwell Automation ThinServer™ and cause a denial-of-service condition on the affected device.
An input validation vulnerability exists in the Rockwell Automation Sequence Manager™ which could allow a malicious user to send malformed packets to the server and cause a denial-of-service condition. If exploited, the device would become unresponsive, and a manual restart will be required for recovery. Additionally, if exploited, there could be a loss of view for the downstream equipment sequences in the controller. Users would not be able to view the status or command the equipment sequences, however the equipment sequence would continue to execute uninterrupted.
A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover.
An input validation vulnerability exists in the Rockwell Automation 5015 - AENFTXT when a manipulated PTP packet is sent, causing the secondary adapter to result in a major nonrecoverable fault. If exploited, a power cycle is required to recover the product.
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running.
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
CVE-2024-45825 IMPACT A denial-of-service vulnerability exists in the affected products. The vulnerability occurs when a malformed CIP packet is sent over the network to the device and results in a major nonrecoverable fault causing a denial-of-service.
FactoryTalk Linx, in the Rockwell Automation PanelView Plus, allows an unauthenticated threat actor to read data from memory via crafted malicious packets. Sending a size larger than the buffer size results in leakage of data from memory resulting in an information disclosure. If the size is large enough, it causes communications over the common industrial protocol to become unresponsive to any type of packet, resulting in a denial-of-service to FactoryTalk Linx over the common industrial protocol.
The Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability, an integer overflow condition exists in the affected products. When the ThinManager processes incoming messages, a read access violation occurs and terminates the process. A malicious user could exploit this vulnerability by sending a crafted synchronization protocol message and causing a denial of service condition in the software.
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.
The Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability. Due to an improper input validation, a path traversal vulnerability exists, via the filename field, when the ThinManager processes a certain function. If exploited, an unauthenticated remote attacker can upload arbitrary files to any directory on the disk drive where ThinServer.exe is installed. A malicious user could exploit this vulnerability by sending a crafted synchronization protocol message and potentially gain remote code execution abilities.
A remote code execution vulnerability exists in the Rockwell Automation ThinManager® ThinServer™ that allows a threat actor to execute arbitrary code with System privileges. This vulnerability exists due to the lack of proper data input validation, which allows files to be overwritten.
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
The Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability, Due to improper input validation, a path traversal vulnerability exists when the ThinManager software processes a certain function. If exploited, an unauthenticated remote threat actor can delete arbitrary files with system privileges. A malicious user could exploit this vulnerability by sending a specifically crafted synchronization protocol message resulting in a denial-of-service condition.
A remote code execution vulnerability exists in the affected product. The vulnerability allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code.
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.
Due to an improper input validation, an unauthenticated threat actor can send a malicious message to invoke SQL injection into the program and cause a remote code execution condition on the Rockwell Automation ThinManager® ThinServer™.
Due to an improper input validation, an unauthenticated threat actor can send a malicious message to invoke a local or remote executable and cause a remote code execution condition on the Rockwell Automation ThinManager® ThinServer™.
A specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices.
A vulnerability exists in the Rockwell Automation FactoryTalk® View SE Datalog function that could allow a threat actor to inject a malicious SQL statement if the SQL database has no authentication in place or if legitimate credentials were stolen. If exploited, the attack could result in information exposure, revealing sensitive information. Additionally, a threat actor could potentially modify and delete the data in a remote database. An attack would only affect the HMI design time, not runtime.
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.