Rockwell Automation FLEX 5000 I/O - Module Fault

A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.

Affected Products
Vendor
Rockwell Automation, Inc.Rockwell Automation
Product
FLEX 5000 I/O
Default Status
unaffected
Versions
Affected
  • Version 2.011 or below
Problem Types
TypeCWE IDDescription
CWECWE-1287CWE-1287: Improper Validation of Specified Type of Input
Metrics
VersionBase scoreBase severityVector
4.08.7HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Metrics Other Info
Impacts
CAPEC IDDescription
Solutions

Upgrade to version 2.012 or later

Configurations

Workarounds

Exploits

Credits

Timeline
EventDate
Replaced By

Rejected Reason

References
HyperlinkResource
https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1737.html
N/A
▼Authorized Data Publishers (ADP)
CISA ADP Vulnrichment
Affected Products
Metrics
VersionBase scoreBase severityVector
Metrics Other Info
Impacts
CAPEC IDDescription
Solutions

Configurations

Workarounds

Exploits

Credits

Timeline
EventDate
Replaced By

Rejected Reason

References
HyperlinkResource
Details not found