CVE-2023-4346
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-7.5||HIGH
EPSS-0.85% / 54.34%
||
7 Day CHG+0.37%
Published-29 Aug, 2023 | 19:38
Updated-16 Jul, 2026 | 05:16
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Known KEV||Action Due Date - 2026-07-29||Apply mitigations in accordance with vendor instructions, ensuring compliance with CISA’s BOD 26-04 Prioritizing Security Updates Based on Risk (see URL in Notes) guidance and CISA’s “Forensics Triage Requirements” (see URL in Notes). Follow applicable BOD 26-04 guidance for cloud services or discontinue use of the product if mitigations are unavailable. Stakeholders are responsible for evaluating each asset's internet exposure and ensuring adherence to BOD 26-04 patching guidelines.

KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.

Action-Not Available
Vendor-knxKNX AssociationKNX Association
Product-connection_authorizationKNX Protocol Connection Authorization Option 1KNX Protocol Connection Authorization Option 1
CWE ID-CWE-645
Overly Restrictive Account Lockout Mechanism