An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: The filetype 0x03 allows users write access, allowing the ability to overwrite the Master Password value stored in the file.
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0012 Fault Type: Non-User Description: A fault state can be triggered by overwriting the ladder logic data file (type 0x22 number 0x02) with null values.
In the MMM::Agent::Helpers::Network::clear_ip function in MySQL Multi-Master Replication Manager (MMM) mmm_agentd 2.2.1 (for FreeBSD), a specially crafted MMM protocol message can cause a shell command injection resulting in arbitrary command execution with the privileges of the mmm\_agentd process. An attacker that can initiate a TCP session with mmm\_agentd can trigger this vulnerability.
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Live rung edits are able to be made by an unauthenticated user allowing for addition, deletion, or modification of existing ladder logic. Additionally, faults and cpu state modification can be triggered if specific ladder logic is used.
In the MMM::Agent::Helpers::Network::add_ip function in MySQL Multi-Master Replication Manager (MMM) mmm_agentd 2.2.1 (for Solaris), a specially crafted MMM protocol message can cause a shell command injection resulting in arbitrary command execution with the privileges of the mmm\_agentd process. An attacker that can initiate a TCP session with mmm\_agentd can trigger this vulnerability.
In the MMM::Agent::Helpers::Network::clear_ip function in MySQL Multi-Master Replication Manager (MMM) mmm_agentd 2.2.1 (for Solaris), a specially crafted MMM protocol message can cause a shell command injection resulting in arbitrary command execution with the privileges of the mmm\_agentd process. An attacker that can initiate a TCP session with mmm\_agentd can trigger this vulnerability.
In the MMM::Agent::Helpers::Network::add_ip function in MySQL Multi-Master Replication Manager (MMM) mmm_agentd 2.2.1 (for Linux), a specially crafted MMM protocol message can cause a shell command injection resulting in arbitrary command execution with the privileges of the mmm\_agentd process. An attacker that can initiate a TCP session with mmm\_agentd can trigger this vulnerability.
An exploitable Use of Hard-coded Credentials vulnerability exists in the Moxa AWK-3131A Wireless Access Point running firmware 1.1. The device operating system contains an undocumented, privileged (root) account with hard-coded credentials, giving attackers full control of affected devices.
An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service.
A deserialization vulnerability exists in how the ArchiveService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier verifies serialized data. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in FactoryTalk AssetCentre.
Rockwell Automation MicroLogix 1400 PLC 1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA devices have a hardcoded SNMP community, which makes it easier for remote attackers to load arbitrary firmware updates by leveraging knowledge of this community.
SQL injection vulnerability in Rockwell Automation FactoryTalk EnergyMetrix before 2.20.00 allows remote attackers to execute arbitrary SQL commands via unspecified vectors.
In Rockwell Automation PanelView 5510 (all versions manufactured before March 13, 2019 that have never been updated to v4.003, v5.002, or later), a remote, unauthenticated threat actor with access to an affected PanelView 5510 Graphic Display, upon successful exploit, may boot-up the terminal and gain root-level access to the device’s file system.
An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.
Rockwell Automation ThinManager ThinServer versions 11.0.0 - 13.0.0 is vulnerable to a heap-based buffer overflow. An attacker could send a specifically crafted TFTP or HTTPS request, causing a heap-based buffer overflow that crashes the ThinServer process. If successfully exploited, this could expose the server to arbitrary remote code execution.
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.
A vulnerability exists in the Rockwell Automation FactoryTalk® View SE Datalog function that could allow a threat actor to inject a malicious SQL statement if the SQL database has no authentication in place or if legitimate credentials were stolen. If exploited, the attack could result in information exposure, revealing sensitive information. Additionally, a threat actor could potentially modify and delete the data in a remote database. An attack would only affect the HMI design time, not runtime.
CVE-2024-45823 IMPACT An authentication bypass vulnerability exists in the affected product. The vulnerability exists due to shared secrets across accounts and could allow a threat actor to impersonate a user if the threat actor is able to enumerate additional information required during authentication.
A Missing Authorization issue was discovered in Rockwell Automation PanelView Plus 6 700-1500 6.00.04, 6.00.05, 6.00.42, 6.00-20140306, 6.10.20121012, 6.10-20140122, 7.00-20121012, 7.00-20130108, 7.00-20130325, 7.00-20130619, 7.00-20140128, 7.00-20140310, 7.00-20140429, 7.00-20140621, 7.00-20140729, 7.00-20141022, 8.00-20140730, and 8.00-20141023. There is no authorization check when connecting to the device, allowing an attacker remote access.
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Any input or output can be forced, causing unpredictable activity from the PLC.
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Requests a specific set of bytes from an undocumented data file and returns the ASCII version of the master password.
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Reads the encoded ladder logic from its data file and print it out in HEX.
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.