CVE-2024-45824
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-9.2||CRITICAL
EPSS-0.57% / 67.58%
||
7 Day CHG~0.00%
Published-12 Sep, 2024 | 14:05
Updated-31 Jan, 2025 | 15:25
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
FactoryTalk® View Site Edition Remote Code Execution Vulnerability via Lack of Input Validation

CVE-2024-45824 IMPACT A remote code vulnerability exists in the affected products. The vulnerability occurs when chained with Path Traversal, Command Injection, and XSS Vulnerabilities and allows for full unauthenticated remote code execution. The link in the mitigations section below contains patches to fix this issue.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View Site Editionfactorytalk_view
CWE ID-CWE-77
Improper Neutralization of Special Elements used in a Command ('Command Injection')
CVE-2024-7513
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-8.5||HIGH
EPSS-0.09% / 25.60%
||
7 Day CHG~0.00%
Published-14 Aug, 2024 | 19:48
Updated-15 Aug, 2025 | 13:03
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk® View Site Edition Code Execution Vulnerability via File Permissions

CVE-2024-7513 IMPACT A code execution vulnerability exists in the affected product. The vulnerability occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View Site Editionfactorytalk_view
CWE ID-CWE-732
Incorrect Permission Assignment for Critical Resource
CVE-2024-37369
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-8.5||HIGH
EPSS-0.01% / 0.27%
||
7 Day CHG~0.00%
Published-14 Jun, 2024 | 16:50
Updated-31 Jan, 2025 | 15:45
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk® View SE Local Privilege Escalation Vulnerability via Local File Permissions

A privilege escalation vulnerability exists in the affected product. The vulnerability allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk® View SEfactorytalk_view
CWE ID-CWE-732
Incorrect Permission Assignment for Critical Resource
CVE-2024-37368
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-8.2||HIGH
EPSS-0.11% / 30.54%
||
7 Day CHG~0.00%
Published-14 Jun, 2024 | 14:30
Updated-31 Jan, 2025 | 15:44
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk® View SE v11 Information Leakage Vulnerability via Authentication Restriction

A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk® View SEfactorytalk_view
CWE ID-CWE-287
Improper Authentication
CWE ID-CWE-306
Missing Authentication for Critical Function
CVE-2024-37367
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-8.2||HIGH
EPSS-0.06% / 20.03%
||
7 Day CHG~0.00%
Published-14 Jun, 2024 | 14:17
Updated-16 Aug, 2024 | 19:29
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk® View SE v12 Information Leakage Vulnerability via Authentication Restriction

A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE v12. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. This action is allowed without proper authentication verification.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk® View SE
CWE ID-CWE-287
Improper Authentication
CVE-2024-4609
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-8.8||HIGH
EPSS-0.20% / 42.25%
||
7 Day CHG~0.00%
Published-16 May, 2024 | 15:13
Updated-30 Jan, 2025 | 15:50
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation Datalog Function within in FactoryTalk® View SE contains SQL Injection Vulnerability

A vulnerability exists in the Rockwell Automation FactoryTalk® View SE Datalog function that could allow a threat actor to inject a malicious SQL statement if the SQL database has no authentication in place or if legitimate credentials were stolen. If exploited, the attack could result in information exposure, revealing sensitive information. Additionally, a threat actor could potentially modify and delete the data in a remote database. An attack would only affect the HMI design time, not runtime.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk® View SEfactorytalk_view
CWE ID-CWE-20
Improper Input Validation
CWE ID-CWE-89
Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection')
CVE-2023-46289
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-7.5||HIGH
EPSS-0.29% / 52.05%
||
7 Day CHG-0.03%
Published-27 Oct, 2023 | 18:28
Updated-27 Feb, 2025 | 20:39
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk® View Site Edition Vulnerable to Improper Input Validation

Rockwell Automation FactoryTalk View Site Edition insufficiently validates user input, which could potentially allow threat actors to send malicious data bringing the product offline. If exploited, the product would become unavailable and require a restart to recover resulting in a denial-of-service condition.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk® View Site Edition
CWE ID-CWE-20
Improper Input Validation
CVE-2023-2071
Assigner-Rockwell Automation
ShareView Details
Assigner-Rockwell Automation
CVSS Score-9.8||CRITICAL
EPSS-0.67% / 70.32%
||
7 Day CHG+0.19%
Published-12 Sep, 2023 | 13:12
Updated-25 Sep, 2024 | 20:05
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
FactoryTalk View Machine Edition Vulnerable to Remote Code Execution

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-panelview_plusfactorytalk_viewFa
CWE ID-CWE-20
Improper Input Validation
CWE ID-CWE-434
Unrestricted Upload of File with Dangerous Type
CVE-2020-14480
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-5.5||MEDIUM
EPSS-0.01% / 1.05%
||
7 Day CHG~0.00%
Published-24 Feb, 2022 | 18:27
Updated-17 Apr, 2025 | 19:15
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker could gain access to certain credentials, including Windows Logon credentials.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View SE
CWE ID-CWE-312
Cleartext Storage of Sensitive Information
CVE-2020-14481
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-7.8||HIGH
EPSS-0.01% / 0.29%
||
7 Day CHG~0.00%
Published-24 Feb, 2022 | 18:27
Updated-17 Apr, 2025 | 19:15
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available

The DeskLock tool provided with FactoryTalk View SE uses a weak encryption algorithm that may allow a local, authenticated attacker to decipher user credentials, including the Windows user or Windows DeskLock passwords. If the compromised user has an administrative account, an attacker could gain full access to the user’s operating system and certain components of FactoryTalk View SE.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View SE
CWE ID-CWE-261
Weak Encoding for Password
CWE ID-CWE-326
Inadequate Encryption Strength
CVE-2020-12028
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-7.3||HIGH
EPSS-30.94% / 96.57%
||
7 Day CHG~0.00%
Published-20 Jul, 2020 | 15:17
Updated-16 Sep, 2024 | 23:26
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk View SE

In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View SE
CWE ID-CWE-264
Not Available
CWE ID-CWE-306
Missing Authentication for Critical Function
CVE-2020-12027
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-4.3||MEDIUM
EPSS-25.91% / 96.06%
||
7 Day CHG~0.00%
Published-20 Jul, 2020 | 15:13
Updated-17 Sep, 2024 | 04:29
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk View SE

All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View SE
CWE ID-CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
CVE-2020-12031
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-7.5||HIGH
EPSS-0.01% / 0.42%
||
7 Day CHG~0.00%
Published-20 Jul, 2020 | 15:10
Updated-16 Sep, 2024 | 16:48
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk View SE

In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View SE
CWE ID-CWE-119
Improper Restriction of Operations within the Bounds of a Memory Buffer
CWE ID-CWE-787
Out-of-bounds Write
CVE-2020-12029
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
ShareView Details
Assigner-Cybersecurity and Infrastructure Security Agency (CISA) Industrial Control Systems (ICS)
CVSS Score-9||CRITICAL
EPSS-27.07% / 96.19%
||
7 Day CHG~0.00%
Published-20 Jul, 2020 | 14:56
Updated-16 Sep, 2024 | 22:02
Rejected-Not Available
Known To Be Used In Ransomware Campaigns?-Not Available
KEV Added-Not Available
KEV Action Due Date-Not Available
Rockwell Automation FactoryTalk View SE

All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.

Action-Not Available
Vendor-Rockwell Automation, Inc.
Product-factorytalk_viewFactoryTalk View SE
CWE ID-CWE-20
Improper Input Validation