A CWE-119: Buffer Errors vulnerability exists in ProClima (all versions prior to version 8.0.0) which allows an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
Multiple buffer overflows in ActUWzd.dll 1.0.0.1 in Mitsubishi MX Component 3, as distributed in Citect CitectFacilities 7.10 and CitectScada 7.10r1, allow remote attackers to execute arbitrary code via a long string, as demonstrated by a long WzTitle property value to a certain ActiveX control.
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.
Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote attackers to execute arbitrary code by sending TCP port-12397 data that does not comply with a protocol.
Stack-based buffer overflow in the GoAhead Web Server on Schneider Electric Modicon M340 PLC BMXNOx and BMXPx devices allows remote attackers to execute arbitrary code via a long password in HTTP Basic Authentication data.
A CWE-119:Improper restriction of operations within the bounds of a memory buffer vulnerability exists in PowerLogic ION7400, PM8000 and ION9000 (All versions prior to V3.0.0), which could cause the meter to reboot or allow for remote code execution.
Stack-based buffer overflow in Schneider Electric Wonderware InTouch Access Anywhere Server 10.6 and 11.0 allows remote attackers to execute arbitrary code via a request for a filename that does not exist.
Buffer overflow in an ActiveX control in Atx45.ocx in Schneider Electric ProClima before 6.1.7 allows remote attackers to execute arbitrary code via unspecified vectors, a different vulnerability than CVE-2014-8512. NOTE: this may be clarified later based on details provided by researchers.
Heap-based buffer overflow in RFManagerService.exe in Schneider Electric Accutech Manager 2.00.1 and earlier allows remote attackers to execute arbitrary code via a crafted HTTP request.
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could allow an attacker to create or overwrite critical files that are used to execute code, such as programs or libraries and cause unauthenticated code execution. Affected Products: EcoStruxure Power Commission (Versions prior to V2.22)
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could allow changes to administrative credentials, leading to potential remote code execution without requiring prior authentication on the Java RMI interface.
CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote code execution when manipulating internal methods through Java RMI interface.
A CWE-129: Improper validation of an array index vulnerability exists where a specially crafted Ethernet request could result in denial of service or remote code execution.
A CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exists that allows remote code execution via the “hostname” parameter when maliciously crafted hostname syntax is entered. Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)
A Format String: CWE-134 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow an attacker to send a crafted message to the target server, thereby causing arbitrary commands to be executed.
A CWE-287: Improper Authentication vulnerability exists in the NET55XX Encoder with firmware prior to version 2.1.9.7 which could cause impact to confidentiality, integrity, and availability when a remote attacker crafts a malicious request to the encoder webUI.
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a remote code execution by overwriting configuration settings of the controller over Modbus.
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-22767
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'network.ieee8021x.delete_certs'.
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port.
The modbus_125_handler function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) allows remote attackers to install arbitrary firmware updates via a MODBUS 125 function code to TCP port 502.
The Schneider Electric Magelis XBT HMI controller has a default password for authentication of configuration uploads, which makes it easier for remote attackers to bypass intended access restrictions via crafted configuration data.
The ComputePassword function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) generates the password for the fwupgrade account by performing a calculation on the MAC address, which makes it easier for remote attackers to obtain access via a (1) ARP request message or (2) Neighbor Solicitation message.
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules.
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service or potential code execution by overwriting configuration settings of the controller over Modbus.
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption.
A CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exists that allows for remote code execution when using a parameter of the DCE network settings endpoint. Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions)
A CWE-306: Missing Authentication for Critical Function The software does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources. Affected Products: APC Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GA), APC Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GA-01-22261), Schneider Electric Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GS), Schneider Electric Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GS-01-22261)
CWE-200: Information Exposure vulnerability exists that could cause disclosure of credentials when a specially crafted message is sent to the device.
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).
Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors.
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution or the crash of HTTPs stack which is used for the device Web HMI. Affected Products: Easergy P5 (V01.401.102 and prior)
A CWE-319: Cleartext transmission of sensitive information vulnerability exists that could cause disclosure of sensitive information, denial of service, or modification of data if an attacker is able to intercept network traffic.
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted setting value messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted time reduced data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted log data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-521: Weak Password Requirements vulnerability exists that could allow an attacker to gain control of the device when the attacker brute forces the password. Affected Products: C-Bus Network Automation Controller - LSS5500NAC (Versions prior to V1.10.0), Wiser for C-Bus Automation Controller - LSS5500SHAC (Versions prior to V1.10.0), Clipsal C-Bus Network Automation Controller - 5500NAC (Versions prior to V1.10.0), Clipsal Wiser for C-Bus Automation Controller - 5500SHAC (Versions prior to V1.10.0), SpaceLogic C-Bus Network Automation Controller - 5500NAC2 (Versions prior to V1.10.0), SpaceLogic C-Bus Application Controller - 5500AC2 (Versions prior to V1.10.0)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted alarm data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted online data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-287: Improper Authentication vulnerability exists that could allow an attacker to gain control of the device when logging into a web page. Affected Products: C-Bus Network Automation Controller - LSS5500NAC (Versions prior to V1.10.0), Wiser for C-Bus Automation Controller - LSS5500SHAC (Versions prior to V1.10.0), Clipsal C-Bus Network Automation Controller - 5500NAC (Versions prior to V1.10.0), Clipsal Wiser for C-Bus Automation Controller - 5500SHAC (Versions prior to V1.10.0), SpaceLogic C-Bus Network Automation Controller - 5500NAC2 (Versions prior to V1.10.0), SpaceLogic C-Bus Application Controller - 5500AC2 (Versions prior to V1.10.0)
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)
A CWE-522: Insufficiently Protected Credentials vulnerability exists that could result in unwanted access to a DCE instance when performed over a network by a malicious third-party. This CVE is unique from CVE-2022-32518. Affected Products: Data Center Expert (Versions prior to V7.9.0)
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could allow arbitrary code to be executed when root level access is obtained. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior)
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow unauthorized access when an attacker uses brute force. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior)
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause modification of an existing file by inserting at beginning of file or create a new file in the context of the Data Server potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22073)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)