A CWE-306: Missing Authentication for Critical Function The software does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources. Affected Products: APC Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GA), APC Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GA-01-22261), Schneider Electric Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GS), Schneider Electric Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GS-01-22261)
A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T200 ((Modbus) SC2-04MOD-07000100 and earlier), Easergy T200 ((IEC104) SC2-04IEC-07000100 and earlier), and Easergy T200 ((DNP3) SC2-04DNP-07000102 and earlier) that could cause unauthorized operation when authentication is bypassed.
A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T300 (with firmware 2.7 and older) that could cause a wide range of problems, including information exposure, denial of service, and command execution when access to a resource from an attacker is not restricted or incorrectly restricted.
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a remote code execution by overwriting configuration settings of the controller over Modbus.
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could allow changes to administrative credentials, leading to potential remote code execution without requiring prior authentication on the Java RMI interface.
In Schneider Electric Evlink Charging Station versions prior to v3.2.0-12_v1, the Web Interface has an issue that may allow a remote attacker to gain administrative privileges without properly authenticating remote users.
A buffer overflow vulnerability exist in the web-based GUI of Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to execute arbitrary code.
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions)
A CWE-319: Cleartext transmission of sensitive information vulnerability exists that could cause disclosure of sensitive information, denial of service, or modification of data if an attacker is able to intercept network traffic.
An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code.
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)
A CWE-434: Unrestricted Upload of File with Dangerous Type vulnerability exists that could cause remote code execution when the attacker uploads a malicious JSP file. Affected Products: APC Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GA), APC Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GA-01-22261), Schneider Electric Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GS), Schneider Electric Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GS-01-22261)
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'network.ieee8021x.delete_certs'.
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service or potential code execution by overwriting configuration settings of the controller over Modbus.
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization.
In Schneider Electric U.motion Builder software versions prior to v1.3.4, this exploit occurs when the submitted data of an input string is evaluated as a command by the application. In this way, the attacker could execute code, read the stack, or cause a segmentation fault in the running application.
A CWE-614 Insufficient Session Expiration vulnerability exists that could allow an attacker to maintain an unauthorized access over a hijacked session to the charger station web server even after the legitimate user account holder has changed his password. Affected Products: EVlink City EVC1S22P4 / EVC1S7P4 (All versions prior to R8 V3.4.0.2 ), EVlink Parking EVW2 / EVF2 / EVP2PE (All versions prior to R8 V3.4.0.2), and EVlink Smart Wallbox EVB1A (All versions prior to R8 V3.4.0.2)
A CWE-259: Use of Hard-coded Password vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to gain unauthorized administrative privileges when accessing to the charging station web server.
A CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause remote code execution. Affected Product: StruxureWare Data Center Expert (V7.8.1 and prior)
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists in PowerLogic PM55xx, PowerLogic PM8ECC, PowerLogic EGX100 and PowerLogic EGX300 (see security notification for version infromation) that could allow an attacker administrator level access to a device.
Insufficiently Protected Credentials vulnerability exists in homeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior that could cause unauthorized access of when credentials are discovered after a brute force attack.
A CWE-331: Insufficient Entropy vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to gain unauthorized access to the charging station web server
A CWE-798: Use of Hard-coded Credentials vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to issue unauthorized commands to the charging station web server with administrative privileges.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and gain administrator privileges because the use of hardcoded credentials.
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on user supplied data, when a constructed message is received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)
A CWE-798: Use of Hard-coded Credentials vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could an attacker to gain unauthorized administrative privileges when accessing to the charging station web server.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'system.opkg.remove'.
A CWE-269: Improper Privilege Management vulnerability exists that could cause an arbitrary command execution when the software is configured with specially crafted event actions. Affected Product: ConneXium Network Manager Software (All Versions)
A CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote code execution when performed over the network. Affected Product: StruxureWare Data Center Expert (V7.8.1 and prior)
Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in homeLYnk (Wiser For KNX) and spaceLYnk V2.60 and prior that could cause unauthorized access when credentials are discovered after a brute force attack.
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-2276
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet
A CWE-119:Improper restriction of operations within the bounds of a memory buffer vulnerability exists in PowerLogic ION7400, PM8000 and ION9000 (All versions prior to V3.0.0), which could cause the meter to reboot or allow for remote code execution.
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes.
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-22767
Weak Password Recovery Mechanism for Forgotten Password vulnerability exists on Modicon Managed Switch MCSESM* and MCSESP* V8.21 and prior which could cause an unauthorized password change through HTTP / HTTPS when basic user information is known by a remote attacker.
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.
An unrestricted Upload of File with Dangerous Type vulnerability exists on numerous methods of the IIoT Monitor 3.1.38 software that could allow upload and execution of malicious files.
A Credentials Management CWE-255 vulnerability exists in the APC UPS Network Management Card 2 AOS v6.5.6, which could cause Remote Monitoring Credentials to be viewed in plaintext when Remote Monitoring is enabled, and then disabled.
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC.
A SQL Injection (CWE-89) vulnerability exists in U.motion Builder software version 1.3.4 which could cause unwanted code execution when an improper set of characters is entered.
A CWE-290: Authentication Bypass by Spoofing vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause an elevation of privilege by conducting a brute force attack on Modbus parameters sent to the controller.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'model_name' or 'mac_address'.
In Schneider Electric U.motion Builder software versions prior to v1.3.4, a remote command injection allows authentication bypass.
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution or the crash of HTTPs stack which is used for the device Web HMI. Affected Products: Easergy P5 (V01.401.102 and prior)
A CWE-501: Trust Boundary Violation vulnerability on connection to the Controller exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum and Modicon Premium which could cause unauthorized access by conducting a brute force attack on Modbus protocol to the controller.
An unspecified ActiveX control in Schneider Electric SoMachine HVAC Programming Software for M171/M172 Controllers before 2.1.0 allows remote attackers to execute arbitrary code via unknown vectors, related to the INTERFACESAFE_FOR_UNTRUSTED_CALLER (aka safe for scripting) flag.
In Schneider Electric Pelco Sarix Professional 1st generation cameras with firmware versions prior to 3.29.69, a buffer overflow vulnerability exist in cgi program "set".
A CWE-257: Storing Passwords in a Recoverable Format vulnerability exists that could result in unwanted access to a DCE instance when performed over a network by a malicious third-party. Affected Products: Data Center Expert (Versions prior to V7.9.0)