A Credentials Management CWE-255 vulnerability exists in the APC UPS Network Management Card 2 AOS v6.5.6, which could cause Remote Monitoring Credentials to be viewed in plaintext when Remote Monitoring is enabled, and then disabled.
An Information Exposure through Discrepancy vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where the web server sends different responses in a way that exposes security-relevant information about the state of the product, such as whether a particular operation was successful or not.
A SQL Injection (CWE-89) vulnerability exists in U.motion Builder software version 1.3.4 which could cause unwanted code execution when an improper set of characters is entered.
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service or potential code execution by overwriting configuration settings of the controller over Modbus.
In Schneider Electric Wiser for KNX V2.1.0 and prior, homeLYnk V2.0.1 and prior; and spaceLYnk V2.1.0 and prior, weak and unprotected FTP access could allow an attacker unauthorized access.
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and gain administrator privileges because the use of hardcoded credentials.
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC.
A CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exists that allows remote code execution via the “hostname” parameter when maliciously crafted hostname syntax is entered. Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)
A CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exists that allows for remote code execution when using a parameter of the DCE network settings endpoint. Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-22767
A CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause remote code execution. Affected Product: StruxureWare Data Center Expert (V7.8.1 and prior)
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on user supplied data, when a constructed message is received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)
A CWE-331: Insufficient Entropy vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to gain unauthorized access to the charging station web server
A CWE-269: Improper Privilege Management vulnerability exists that could cause an arbitrary command execution when the software is configured with specially crafted event actions. Affected Product: ConneXium Network Manager Software (All Versions)
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in SFAPV9601 - APC Easy UPS On-Line Software (V2.0 and earlier) when accessing a vulnerable method of `SoundUploadServlet` which may lead to uploading executable files to non-specified directories.
A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists which could allow the attacker to execute malicious code on the Modicon M218, M241, M251, and M258 controllers.
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in EcoStruxure Operator Terminal Expert 3.1 Service Pack 1 and prior (formerly known as Vijeo XD)which could cause arbitrary application execution when the computer starts.
A CWE-200: Information Exposure vulnerability exists in Easergy T300, Firmware V1.5.2 and prior, which could allow an attacker to pack or unpack the archive with the firmware for the controller and modules using the usual tar archiver resulting in an information exposure.
**VERSION NOT SUPPORTED WHEN ASSIGNED** A vulnerability could cause certain data to be visible on the network when the 'password' feature is enabled. This vulnerability was discovered in and remediated in versions v4.9.1 and v4.10.1 on May 30, 2013. The 'password' feature is an additional optional check performed by TS1131 that it is connected to a specific controller. This data is sent as clear text and is visible on the network. This feature is not present in TriStation 1131 versions v4.9.1 and v4.10.1 through current. Therefore, the vulnerability is not present in these versions.
A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists which could leak sensitive information transmitted between the software and the Modicon M218, M241, M251, and M258 controllers.
A CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to acquire a password by brute force.
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the transference of malicious code to the controller.
A CWE-312: Cleartext Storage of Sensitive Information vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to intercept traffic and read configuration data.
A CWE-319: Cleartext transmission of sensitive information vulnerability exists that could cause disclosure of sensitive information, denial of service, or modification of data if an attacker is able to intercept network traffic.
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions)
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)
A CWE-306: Missing Authentication for Critical Function The software does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources. Affected Products: APC Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GA), APC Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GA-01-22261), Schneider Electric Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GS), Schneider Electric Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GS-01-22261)
A CWE-434: Unrestricted Upload of File with Dangerous Type vulnerability exists that could cause remote code execution when the attacker uploads a malicious JSP file. Affected Products: APC Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GA), APC Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GA-01-22261), Schneider Electric Easy UPS Online Monitoring Software (Windows 7, 10, 11 & Windows Server 2016, 2019, 2022 - Versions prior to V2.5-GS), Schneider Electric Easy UPS Online Monitoring Software (Windows 11, Windows Server 2019, 2022 - Versions prior to V2.5-GS-01-22261)
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Easergy T300 (firmware 2.7 and older), that would allow an attacker to read network traffic over HTTP protocol.
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Easergy T300 (firmware 2.7 and older), that would allow an attacker to read network traffic over HTTP protocol.
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution or the crash of HTTPs stack which is used for the device Web HMI. Affected Products: Easergy P5 (V01.401.102 and prior)
CWE-862: Missing Authorization vulnerability exists that could cause unauthorized access when enabled on the network and potentially impacting connected devices.
A CWE-521: Weak Password Requirements vulnerability exists that could allow an attacker to gain control of the device when the attacker brute forces the password. Affected Products: C-Bus Network Automation Controller - LSS5500NAC (Versions prior to V1.10.0), Wiser for C-Bus Automation Controller - LSS5500SHAC (Versions prior to V1.10.0), Clipsal C-Bus Network Automation Controller - 5500NAC (Versions prior to V1.10.0), Clipsal Wiser for C-Bus Automation Controller - 5500SHAC (Versions prior to V1.10.0), SpaceLogic C-Bus Network Automation Controller - 5500NAC2 (Versions prior to V1.10.0), SpaceLogic C-Bus Application Controller - 5500AC2 (Versions prior to V1.10.0)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted online data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted mathematically reduced data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted setting value messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-257: Storing Passwords in a Recoverable Format vulnerability exists that could result in unwanted access to a DCE instance when performed over a network by a malicious third-party. Affected Products: Data Center Expert (Versions prior to V7.9.0)
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in a function that could allow an attacker to create or overwrite critical files that are used to execute code, such as programs or libraries and cause path traversal attacks. Affected Products: EcoStruxure Power Commission (Versions prior to V2.22)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted alarm cache data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted alarm data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted time reduced data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted log data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-522: Insufficiently Protected Credentials vulnerability exists that could result in unwanted access to a DCE instance when performed over a network by a malicious third-party. This CVE is unique from CVE-2022-32518. Affected Products: Data Center Expert (Versions prior to V7.9.0)
A CWE-522: Insufficiently Protected Credentials vulnerability exists that could result in unwanted access to a DCE instance when performed over a network by a malicious third-party. This CVE is unique from CVE-2022-32520. Affected Products: Data Center Expert (Versions prior to V7.9.0)
A CWE-862: Missing Authorization vulnerability exists in Easergy T300 (firmware 2.7 and older), that could cause a wide range of problems, including information exposures, denial of service, and arbitrary code execution when access control checks are not applied consistently.
A CWE-20: Improper Input Validation vulnerability exists in EcoStruxure™ Operator Terminal Expert and Pro-face BLUE (version details in the notification) that could cause arbitrary code execution when the Ethernet Download feature is enable on the HMI.
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could allow arbitrary code to be executed when root level access is obtained. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior)