A vulnerability has been identified in SiNVR/SiVMS Video Server (All versions < V5.0.0). The HTTP service (default port 5401/tcp) of the SiVMS/SiNVR Video Server contains an authentication bypass vulnerability, even when properly configured with enforced authentication. A remote attacker with network access to the Video Server could exploit this vulnerability to read the SiVMS/SiNVR users database, including the passwords of all users in obfuscated cleartext.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The AdminService is available without authentication on the Application Server. An attacker can use methods exposed via this interface to receive password hashes of other users and to change user passwords. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 and newer (All versions), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 and newer (All versions). An attacker with network access to affected installations, which are configured without "Encrypted Communication", can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in Desigo PXC00-E.D V4.10 (All versions < V4.10.111), Desigo PXC00-E.D V5.00 (All versions < V5.0.171), Desigo PXC00-E.D V5.10 (All versions < V5.10.69), Desigo PXC00-E.D V6.00 (All versions < V6.0.204), Desigo PXC00/64/128-U V4.10 (All versions < V4.10.111 only with web module), Desigo PXC00/64/128-U V5.00 (All versions < V5.0.171 only with web module), Desigo PXC00/64/128-U V5.10 (All versions < V5.10.69 only with web module), Desigo PXC00/64/128-U V6.00 (All versions < V6.0.204 only with web module), Desigo PXC001-E.D V4.10 (All versions < V4.10.111), Desigo PXC001-E.D V5.00 (All versions < V5.0.171), Desigo PXC001-E.D V5.10 (All versions < V5.10.69), Desigo PXC001-E.D V6.00 (All versions < V6.0.204), Desigo PXC100-E.D V4.10 (All versions < V4.10.111), Desigo PXC100-E.D V5.00 (All versions < V5.0.171), Desigo PXC100-E.D V5.10 (All versions < V5.10.69), Desigo PXC100-E.D V6.00 (All versions < V6.0.204), Desigo PXC12-E.D V4.10 (All versions < V4.10.111), Desigo PXC12-E.D V5.00 (All versions < V5.0.171), Desigo PXC12-E.D V5.10 (All versions < V5.10.69), Desigo PXC12-E.D V6.00 (All versions < V6.0.204), Desigo PXC200-E.D V4.10 (All versions < V4.10.111), Desigo PXC200-E.D V5.00 (All versions < V5.0.171), Desigo PXC200-E.D V5.10 (All versions < V5.10.69), Desigo PXC200-E.D V6.00 (All versions < V6.0.204), Desigo PXC22-E.D V4.10 (All versions < V4.10.111), Desigo PXC22-E.D V5.00 (All versions < V5.0.171), Desigo PXC22-E.D V5.10 (All versions < V5.10.69), Desigo PXC22-E.D V6.00 (All versions < V6.0.204), Desigo PXC22.1-E.D V4.10 (All versions < V4.10.111), Desigo PXC22.1-E.D V5.00 (All versions < V5.0.171), Desigo PXC22.1-E.D V5.10 (All versions < V5.10.69), Desigo PXC22.1-E.D V6.00 (All versions < V6.0.204), Desigo PXC36.1-E.D V4.10 (All versions < V4.10.111), Desigo PXC36.1-E.D V5.00 (All versions < V5.0.171), Desigo PXC36.1-E.D V5.10 (All versions < V5.10.69), Desigo PXC36.1-E.D V6.00 (All versions < V6.0.204), Desigo PXC50-E.D V4.10 (All versions < V4.10.111), Desigo PXC50-E.D V5.00 (All versions < V5.0.171), Desigo PXC50-E.D V5.10 (All versions < V5.10.69), Desigo PXC50-E.D V6.00 (All versions < V6.0.204), Desigo PXM20-E V4.10 (All versions < V4.10.111), Desigo PXM20-E V5.00 (All versions < V5.0.171), Desigo PXM20-E V5.10 (All versions < V5.10.69), Desigo PXM20-E V6.00 (All versions < V6.0.204). A remote attacker with network access to the device could potentially upload a new firmware image to the devices without prior authentication.
The Telnet service of the SIMATIC HMI Comfort Panels system component in affected products does not require authentication, which may allow a remote attacker to gain access to the device if the service is enabled. Telnet is disabled by default on the SINAMICS Medium Voltage Products (SINAMICS SL150: All versions, SINAMICS SM150: All versions, SINAMICS SM150i: All versions).
A vulnerability has been identified in InterMesh 7177 Hybrid 2.0 Subscriber (All versions < V8.2.12), InterMesh 7707 Fire Subscriber (All versions < V7.2.12 only if the IP interface is enabled (which is not the default configuration)). The web server of affected devices does not authenticate GET requests that execute specific commands (such as `ping`) on operating system level.
A vulnerability has been identified in SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.4.24). Affected devices do not properly authenticate configuration connections. This could allow an unauthenticated remote attacker to access the configuration data.
A vulnerability has been identified in TeleControl Server Basic V3.1 (All versions >= V3.1.2.2 < V3.1.2.3). The affected application contains an information disclosure vulnerability. This could allow an unauthenticated remote attacker to obtain password hashes of users and to login to and perform authenticated operations of the database service.
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). A service available on port 10005/tcp of the affected devices could allow complete access to all services without authorization. An attacker could gain full control over an affected device, if he has access to this service. The system manual recommends to protect access to this port.
A vulnerability has been identified in SINEC NMS (All versions < V4.0). The affected application exposes an endpoint that allows an unauthorized modification of administrative credentials. This could allow an unauthenticated attacker to reset the superadmin password and gain full control of the application (ZDI-CAN-26569).
A vulnerability has been identified in SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions < V16 Update 3a), SIMATIC HMI KTP Mobile Panels (All versions < V16 Update 3a), SINAMICS GH150 (All versions), SINAMICS GL150 (with option X30) (All versions), SINAMICS GM150 (with option X30) (All versions), SINAMICS SH150 (All versions), SINAMICS SL150 (All versions), SINAMICS SM120 (All versions), SINAMICS SM150 (All versions), SINAMICS SM150i (All versions). Affected devices with enabled telnet service do not require authentication for this service. This could allow a remote attacker to gain full access to the device. (ZDI-CAN-12046)
A vulnerability has been identified in SICAM MMU (All versions < V2.05), SICAM SGU (All versions), SICAM T (All versions < V2.18). An attacker with access to the device's web server might be able to execute administrative commands without authentication.
A vulnerability has been identified in SCALANCE X204RNA (HSR), SCALANCE X204RNA (PRP), SCALANCE X204RNA EEC (HSR), SCALANCE X204RNA EEC (PRP), SCALANCE X204RNA EEC (PRP/HSR), SCALANCE X302-7 EEC (230V), SCALANCE X302-7 EEC (230V, coated), SCALANCE X302-7 EEC (24V), SCALANCE X302-7 EEC (24V, coated), SCALANCE X302-7 EEC (2x 230V), SCALANCE X302-7 EEC (2x 230V, coated), SCALANCE X302-7 EEC (2x 24V), SCALANCE X302-7 EEC (2x 24V, coated), SCALANCE X304-2FE, SCALANCE X306-1LD FE, SCALANCE X307-2 EEC (230V), SCALANCE X307-2 EEC (230V, coated), SCALANCE X307-2 EEC (24V), SCALANCE X307-2 EEC (24V, coated), SCALANCE X307-2 EEC (2x 230V), SCALANCE X307-2 EEC (2x 230V, coated), SCALANCE X307-2 EEC (2x 24V), SCALANCE X307-2 EEC (2x 24V, coated), SCALANCE X307-3, SCALANCE X307-3, SCALANCE X307-3LD, SCALANCE X307-3LD, SCALANCE X308-2, SCALANCE X308-2, SCALANCE X308-2LD, SCALANCE X308-2LD, SCALANCE X308-2LH, SCALANCE X308-2LH, SCALANCE X308-2LH+, SCALANCE X308-2LH+, SCALANCE X308-2M, SCALANCE X308-2M, SCALANCE X308-2M PoE, SCALANCE X308-2M PoE, SCALANCE X308-2M TS, SCALANCE X308-2M TS, SCALANCE X310, SCALANCE X310, SCALANCE X310FE, SCALANCE X310FE, SCALANCE X320-1 FE, SCALANCE X320-1-2LD FE, SCALANCE X408-2, SCALANCE XR324-12M (230V, ports on front), SCALANCE XR324-12M (230V, ports on front), SCALANCE XR324-12M (230V, ports on rear), SCALANCE XR324-12M (230V, ports on rear), SCALANCE XR324-12M (24V, ports on front), SCALANCE XR324-12M (24V, ports on front), SCALANCE XR324-12M (24V, ports on rear), SCALANCE XR324-12M (24V, ports on rear), SCALANCE XR324-12M TS (24V), SCALANCE XR324-12M TS (24V), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (24V, ports on front), SCALANCE XR324-4M EEC (24V, ports on front), SCALANCE XR324-4M EEC (24V, ports on rear), SCALANCE XR324-4M EEC (24V, ports on rear), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (2x 24V, ports on front), SCALANCE XR324-4M EEC (2x 24V, ports on front), SCALANCE XR324-4M EEC (2x 24V, ports on rear), SCALANCE XR324-4M EEC (2x 24V, ports on rear), SCALANCE XR324-4M PoE (230V, ports on front), SCALANCE XR324-4M PoE (230V, ports on rear), SCALANCE XR324-4M PoE (24V, ports on front), SCALANCE XR324-4M PoE (24V, ports on rear), SCALANCE XR324-4M PoE TS (24V, ports on front), SIPLUS NET SCALANCE X308-2. Affected devices contain a vulnerability that allows an unauthenticated attacker to violate access-control rules. The vulnerability can be triggered by sending GET request to specific uniform resource locator on the web configuration interface of the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. An attacker could use the vulnerability to obtain sensitive information or change the device configuration. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Attackers with access to port 10005/tcp could perform device reconfigurations and obtain project files from the devices. The system manual recommends to protect access to this port. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). There is a missing authentication verification for a resource used to change the roles and permissions of a user. This could allow an attacker to change the permissions of any user and gain the privileges of an administrative user.
pragma.c in SQLite through 3.30.1 mishandles NOT NULL in an integrity_check PRAGMA command in certain cases of generated columns.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could gain remote code execution by sending specifically crafted objects to one of the RPC services. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted objects via RMI. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
In Network Security Services (NSS) before 3.46, several cryptographic primitives had missing length checks. In cases where the application calling the library did not perform a sanity check on the inputs it could result in a crash due to a buffer overflow.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 1099/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The Control Center Server (CCS) contains an authentication bypass vulnerability in its XML-based communication protocol as provided by default on ports 5444/tcp and 5440/tcp. A remote attacker with network access to the CCS server could exploit this vulnerability to read the CCS users database, including the passwords of all users in obfuscated cleartext.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The AdminService is available without authentication on the Application Server. An attacker can gain remote code execution by sending specifically crafted objects to one of its functions. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18293, CVE-2019-18295, and CVE-2019-18296. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The SFTP service (default port 22/tcp) of the Control Center Server (CCS) does not properly limit its capabilities to the specified purpose. In conjunction with CVE-2019-18341, an unauthenticated remote attacker with network access to the CCS server could exploit this vulnerability to read or delete arbitrary files, or access other resources on the same server.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18289, CVE-2019-18293, and CVE-2019-18296. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18289, CVE-2019-18293, and CVE-2019-18295. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 8888/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18329. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
An arbitrary file copy vulnerability in mod_copy in ProFTPD up to 1.3.5b allows for remote code execution and information disclosure without authentication, a related issue to CVE-2015-3306.
Wind River VxWorks 6.9 and vx7 has a Buffer Overflow in the TCP component (issue 2 of 4). This is an IPNET security vulnerability: TCP Urgent Pointer state confusion caused by a malformed TCP AO option.
Wind River VxWorks has a Buffer Overflow in the TCP component (issue 1 of 4). This is a IPNET security vulnerability: TCP Urgent Pointer = 0 that leads to an integer underflow.
A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'VerifyUser' method. This could allow an unauthenticated remote attacker to bypass authorization controls, to read from and write to the application's database and execute code with "NT AUTHORITY\NetworkService" permissions. A successful attack requires the attacker to be able to access port 8000 on a system where a vulnerable version of the affected application is executed on. (ZDI-CAN-25914)
Wind River VxWorks 6.6, 6.7, 6.8, 6.9 and 7 has Incorrect Access Control in the RARP client component. IPNET security vulnerability: Handling of unsolicited Reverse ARP replies (Logical Flaw).
A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). The webserver of affected devices calculates session ids and nonces in an insecure manner. This could allow an unauthenticated remote attacker to brute-force session ids and hijack existing sessions.
A vulnerability has been identified in TIM 3V-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3). The affected versions contain an open debug port that is available under certain specific conditions. The vulnerability is only available if the IP address is configured to 192.168.1.2. If available, the debug port could be exploited by an attacker with network access to the device. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.
A vulnerability has been identified in SIPROTEC 5 devices with CPU variants CP200 (All versions < V7.59), SIPROTEC 5 devices with CPU variants CP300 and CP100 (All versions < V8.01), Siemens Power Meters Series 9410 (All versions < V2.2.1), Siemens Power Meters Series 9810 (All versions). An unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability in Siemens SICAM PAS (all versions before V8.09) could allow a remote attacker to cause a Denial of Service condition and potentially lead to unauthenticated remote code execution by sending specially crafted packets to port 19234/TCP.
A vulnerability has been identified in OZW672 (All versions < V8.0), OZW772 (All versions < V8.0). The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.
A vulnerability has been identified in OZW672 (All versions < V6.0), OZW772 (All versions < V6.0). The web service of affected devices is vulnerable to SQL injection when checking authentication data. This could allow an unauthenticated remote attacker to bypass the check and authenticate as Administrator user.
A remote code execution vulnerability exists in Remote Desktop Services formerly known as Terminal Services when an unauthenticated attacker connects to the target system using RDP and sends specially crafted requests, aka 'Remote Desktop Services Remote Code Execution Vulnerability'.
A vulnerability has been identified in Mendix SAML (Mendix 7 compatible) (All versions < V1.17.0), Mendix SAML (Mendix 7 compatible) (All versions >= V1.17.0 < V1.17.2), Mendix SAML (Mendix 8 compatible) (All versions < V2.3.0), Mendix SAML (Mendix 8 compatible) (All versions >= V2.3.0 < V2.3.2), Mendix SAML (Mendix 9 compatible, New Track) (All versions < V3.3.1), Mendix SAML (Mendix 9 compatible, New Track) (All versions >= V3.3.1 < V3.3.5), Mendix SAML (Mendix 9 compatible, Upgrade Track) (All versions < V3.3.0), Mendix SAML (Mendix 9 compatible, Upgrade Track) (All versions >= V3.3.0 < V3.3.4). Affected versions of the module insufficiently protect from packet capture replay, only when the not recommended, non default configuration option `'Allow Idp Initiated Authentication'` is enabled. This CVE entry describes the incomplete fix for CVE-2022-37011 in a specific non default configuration.
SINAMICS medium voltage routable products are affected by a vulnerability in the Sm@rtServer component for remote access that could allow an unauthenticated attacker to cause a denial-of-service condition, and/or execution of limited configuration modifications and/or execution of limited control commands on the SINAMICS Medium Voltage Products, Remote Access (SINAMICS SL150: All versions, SINAMICS SM150: All versions, SINAMICS SM150i: All versions).
An issue was discovered in Siemens SICAM PAS before 8.00. A factory account with hard-coded passwords is present in the SICAM PAS installations. Attackers might gain privileged access to the database over Port 2638/TCP.