The Diffie-Hellman Key Agreement Protocol allows remote attackers (from the client side) to send arbitrary numbers that are actually not public keys, and trigger expensive server-side DHE modular-exponentiation calculations, aka a D(HE)at or D(HE)ater attack. The client needs very little CPU resources and network bandwidth. The attack may be more disruptive in cases where a client can require a server to select its largest supported key size. The basic attack scenario is that the client must claim that it can only communicate with DHE, and the server must be configured to allow DHE.
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versions), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), SIMOTICS CONNECT 400 (All versions < V1.0.0.0). The total length of an TCP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on the network buffer organization in memory. (FSMD-2021-0017)
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versions), SIMOTICS CONNECT 400 (All versions < V0.5.0.0). Malformed TCP packets with a corrupted SACK option leads to Information Leaks and Denial-of-Service conditions. (FSMD-2021-0015)
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). When processing a DHCP ACK message, the DHCP client application does not validate the length of the Vendor option(s), leading to Denial-of-Service conditions. (FSMD-2021-0013)
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
A vulnerability has been identified in SCALANCE X302-7 EEC (230V), SCALANCE X302-7 EEC (230V, coated), SCALANCE X302-7 EEC (24V), SCALANCE X302-7 EEC (24V, coated), SCALANCE X302-7 EEC (2x 230V), SCALANCE X302-7 EEC (2x 230V, coated), SCALANCE X302-7 EEC (2x 24V), SCALANCE X302-7 EEC (2x 24V, coated), SCALANCE X304-2FE, SCALANCE X306-1LD FE, SCALANCE X307-2 EEC (230V), SCALANCE X307-2 EEC (230V, coated), SCALANCE X307-2 EEC (24V), SCALANCE X307-2 EEC (24V, coated), SCALANCE X307-2 EEC (2x 230V), SCALANCE X307-2 EEC (2x 230V, coated), SCALANCE X307-2 EEC (2x 24V), SCALANCE X307-2 EEC (2x 24V, coated), SCALANCE X307-3, SCALANCE X307-3, SCALANCE X307-3LD, SCALANCE X307-3LD, SCALANCE X308-2, SCALANCE X308-2, SCALANCE X308-2LD, SCALANCE X308-2LD, SCALANCE X308-2LH, SCALANCE X308-2LH, SCALANCE X308-2LH+, SCALANCE X308-2LH+, SCALANCE X308-2M, SCALANCE X308-2M, SCALANCE X308-2M PoE, SCALANCE X308-2M PoE, SCALANCE X308-2M TS, SCALANCE X308-2M TS, SCALANCE X310, SCALANCE X310, SCALANCE X310FE, SCALANCE X310FE, SCALANCE X320-1 FE, SCALANCE X320-1-2LD FE, SCALANCE X408-2, SCALANCE XR324-12M (230V, ports on front), SCALANCE XR324-12M (230V, ports on front), SCALANCE XR324-12M (230V, ports on rear), SCALANCE XR324-12M (230V, ports on rear), SCALANCE XR324-12M (24V, ports on front), SCALANCE XR324-12M (24V, ports on front), SCALANCE XR324-12M (24V, ports on rear), SCALANCE XR324-12M (24V, ports on rear), SCALANCE XR324-12M TS (24V), SCALANCE XR324-12M TS (24V), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (24V, ports on front), SCALANCE XR324-4M EEC (24V, ports on front), SCALANCE XR324-4M EEC (24V, ports on rear), SCALANCE XR324-4M EEC (24V, ports on rear), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (2x 24V, ports on front), SCALANCE XR324-4M EEC (2x 24V, ports on front), SCALANCE XR324-4M EEC (2x 24V, ports on rear), SCALANCE XR324-4M EEC (2x 24V, ports on rear), SCALANCE XR324-4M PoE (230V, ports on front), SCALANCE XR324-4M PoE (230V, ports on rear), SCALANCE XR324-4M PoE (24V, ports on front), SCALANCE XR324-4M PoE (24V, ports on rear), SCALANCE XR324-4M PoE TS (24V, ports on front), SIPLUS NET SCALANCE X308-2. Affected devices do not properly validate the GET parameter XNo of incoming HTTP requests. This could allow an unauthenticated remote attacker to crash affected devices.
SQLite through 3.31.1 allows attackers to cause a denial of service (segmentation fault) via a malformed window-function query because the AggInfo object's initialization is mishandled.
An issue was discovered in tcp_rcv() in nptcp.c in HCC embedded InterNiche 4.0.1. The TCP header processing code doesn't sanitize the value of the IP total length field (header length + data length). With a crafted IP packet, an integer overflow occurs whenever the value of the IP data length is calculated by subtracting the length of the header from the total length of the IP packet.
UltraVNC revision 1206 has stack-based Buffer overflow vulnerability in VNC client code inside FileTransfer module, which leads to a denial of service (DoS) condition. This attack appear to be exploitable via network connectivity. This vulnerability has been fixed in revision 1207.
Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.10), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants) (All versions < V10.1), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions < V8.2.3), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a Denial-of-Service condition. A restart is needed to restore normal operations.
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4), SINAMICS GH150 (All versions), SINAMICS GL150 (with option X30) (All versions), SINAMICS GM150 (with option X30) (All versions), SINAMICS SH150 (All versions), SINAMICS SL150 (All versions), SINAMICS SM120 (All versions), SINAMICS SM150 (All versions), SINAMICS SM150i (All versions). SmartVNC has a heap allocation leak vulnerability in the server Tight encoder, which could result in a Denial-of-Service condition.
ssri 5.2.2-8.0.0, fixed in 8.0.1, processes SRIs using a regular expression which is vulnerable to a denial of service. Malicious SRIs could take an extremely long time to process, leading to denial of service. This issue only affects consumers using the strict option.
A vulnerability has been identified in SIPROTEC 4 6MD61 (All versions), SIPROTEC 4 6MD63 (All versions), SIPROTEC 4 6MD66 (All versions), SIPROTEC 4 6MD665 (All versions), SIPROTEC 4 7SA522 (All versions), SIPROTEC 4 7SA6 (All versions < V4.78), SIPROTEC 4 7SD5 (All versions < V4.78), SIPROTEC 4 7SD610 (All versions < V4.78), SIPROTEC 4 7SJ61 (All versions), SIPROTEC 4 7SJ62 (All versions), SIPROTEC 4 7SJ63 (All versions), SIPROTEC 4 7SJ64 (All versions), SIPROTEC 4 7SJ66 (All versions), SIPROTEC 4 7SS52 (All versions), SIPROTEC 4 7ST6 (All versions), SIPROTEC 4 7UM61 (All versions), SIPROTEC 4 7UM62 (All versions), SIPROTEC 4 7UT612 (All versions), SIPROTEC 4 7UT613 (All versions), SIPROTEC 4 7UT63 (All versions), SIPROTEC 4 7VE6 (All versions), SIPROTEC 4 7VK61 (All versions), SIPROTEC 4 7VU683 (All versions), SIPROTEC 4 Compact 7RW80 (All versions), SIPROTEC 4 Compact 7SD80 (All versions), SIPROTEC 4 Compact 7SJ80 (All versions), SIPROTEC 4 Compact 7SJ81 (All versions), SIPROTEC 4 Compact 7SK80 (All versions), SIPROTEC 4 Compact 7SK81 (All versions). Affected devices do not properly handle interrupted operations of file transfer. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the devices need to be restarted.
In BIND 9.0.0 -> 9.11.29, 9.12.0 -> 9.16.13, and versions BIND 9.9.3-S1 -> 9.11.29-S1 and 9.16.8-S1 -> 9.16.13-S1 of BIND Supported Preview Edition, as well as release versions 9.17.0 -> 9.17.11 of the BIND 9.17 development branch, when a vulnerable version of named receives a query for a record triggering the flaw described above, the named process will terminate due to a failed assertion check. The vulnerability affects all currently maintained BIND 9 branches (9.11, 9.11-S, 9.16, 9.16-S, 9.17) as well as all other versions of BIND 9.
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (All versions including affected IPv6 stack). The function that processes the Hop-by-Hop extension header in IPv6 packets and its options lacks any checks against the length field of the header, allowing attackers to put the function into an infinite loop by supplying arbitrary length values.
A vulnerability has been identified in RUGGEDCOM RM1224 (V6.3), SCALANCE M-800 (V6.3), SCALANCE S615 (V6.3), SCALANCE SC-600 (All Versions >= V2.1 and < V2.1.3). Multiple failed SSH authentication attempts could trigger a temporary Denial-of-Service under certain conditions. When triggered, the device will reboot automatically.
The process_packet function in ntp_proto.c in ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (peer-variable modification) by sending spoofed packets from many source IP addresses in a certain scenario, as demonstrated by triggering an incorrect leap indication.
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4). SmartVNC has an out-of-bounds memory access vulnerability that could be triggered on the client side when sending data from the server, which could result in a Denial-of-Service condition.
A remote denial of service (dos) vulnerability was discovered in some Aruba Instant Access Point (IAP) products in version(s): Aruba Instant 8.3.x: 8.3.0.12 and below; Aruba Instant 8.5.x: 8.5.0.9 and below; Aruba Instant 8.6.x: 8.6.0.4 and below. Aruba has released patches for Aruba Instant that address this security vulnerability.
UltraVNC revision 1211 has a stack buffer overflow vulnerability in VNC server code inside file transfer request handler, which can result in Denial of Service (DoS). This attack appears to be exploitable via network connectivity. This vulnerability has been fixed in revision 1212.
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4). SmartVNC client fails to handle an exception properly if the program execution process is modified after sending a packet from the server, which could result in a Denial-of-Service condition.
ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (ephemeral-association demobilization) by sending a spoofed crypto-NAK packet with incorrect authentication data at a certain time.
A vulnerability has been identified in Automation License Manager 5 (All versions), Automation License Manager 6 (All versions < V6.0 SP9 Update 2). Sending specially crafted packets to port 4410/tcp of an affected system could lead to extensive memory being consumed and as such could cause a denial-of-service preventing legitimate users from using the system.
A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4). SmartVNC has an out-of-bounds memory access vulnerability that could be triggered on the server side when sending data from the client, which could result in a Denial-of-Service condition.
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (All versions including affected IPv6 stack). The function that processes IPv6 headers does not check the lengths of extension header options, allowing attackers to put this function into an infinite loop with crafted length values.
A vulnerability has been identified in SIMATIC S7-200 SMART CPU CR40 (6ES7288-1CR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU CR60 (6ES7288-1CR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA1) (All versions). Affected devices do not properly handle TCP packets with an incorrect structure. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the network cable of the device needs to be unplugged and re-plugged.
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SIMATIC Reader RF610R CMIIT (6GT2811-6BC10-2AA0) (All versions < V4.2), SIMATIC Reader RF610R ETSI (6GT2811-6BC10-0AA0) (All versions < V4.2), SIMATIC Reader RF610R FCC (6GT2811-6BC10-1AA0) (All versions < V4.2), SIMATIC Reader RF615R CMIIT (6GT2811-6CC10-2AA0) (All versions < V4.2), SIMATIC Reader RF615R ETSI (6GT2811-6CC10-0AA0) (All versions < V4.2), SIMATIC Reader RF615R FCC (6GT2811-6CC10-1AA0) (All versions < V4.2), SIMATIC Reader RF650R ARIB (6GT2811-6AB20-4AA0) (All versions < V4.2), SIMATIC Reader RF650R CMIIT (6GT2811-6AB20-2AA0) (All versions < V4.2), SIMATIC Reader RF650R ETSI (6GT2811-6AB20-0AA0) (All versions < V4.2), SIMATIC Reader RF650R FCC (6GT2811-6AB20-1AA0) (All versions < V4.2), SIMATIC Reader RF680R ARIB (6GT2811-6AA10-4AA0) (All versions < V4.2), SIMATIC Reader RF680R CMIIT (6GT2811-6AA10-2AA0) (All versions < V4.2), SIMATIC Reader RF680R ETSI (6GT2811-6AA10-0AA0) (All versions < V4.2), SIMATIC Reader RF680R FCC (6GT2811-6AA10-1AA0) (All versions < V4.2), SIMATIC Reader RF685R ARIB (6GT2811-6CA10-4AA0) (All versions < V4.2), SIMATIC Reader RF685R CMIIT (6GT2811-6CA10-2AA0) (All versions < V4.2), SIMATIC Reader RF685R ETSI (6GT2811-6CA10-0AA0) (All versions < V4.2), SIMATIC Reader RF685R FCC (6GT2811-6CA10-1AA0) (All versions < V4.2), SIMATIC RF1140R (6GT2831-6CB00) (All versions < V1.1), SIMATIC RF1170R (6GT2831-6BB00) (All versions < V1.1), SIMATIC RF166C (6GT2002-0EE20) (All versions < V2.2), SIMATIC RF185C (6GT2002-0JE10) (All versions < V2.2), SIMATIC RF186C (6GT2002-0JE20) (All versions < V2.2), SIMATIC RF186CI (6GT2002-0JE50) (All versions < V2.2), SIMATIC RF188C (6GT2002-0JE40) (All versions < V2.2), SIMATIC RF188CI (6GT2002-0JE60) (All versions < V2.2), SIMATIC RF360R (6GT2801-5BA30) (All versions < V2.2). The affected devices does not properly handle the error in case of exceeding characters while setting SNMP leading to the restart of the application.
A vulnerability has been identified in SINAMICS PERFECT HARMONY GH180 with NXG I control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G28), SINAMICS PERFECT HARMONY GH180 with NXG II control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G28). A denial of service vulnerability exists in the affected products. The vulnerability could be exploited by an attacker with network access to the device. Successful exploitation requires no privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
Triangle Microworks TMW IEC 61850 Client source code libraries before 12.2.0 lack a buffer size check when processing received messages. The resulting buffer overflow can cause a crash, resulting in a denial of service.
A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). An attacker with network access to port 10005/tcp of the LOGO! device could cause a Denial-of-Service condition by sending specially crafted packets. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation of the security vulnerability compromises availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions < V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions < V1.1.0), SIMATIC RF600R family (All versions < V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 < V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions < V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Upd 4), SINEC NMS (All versions < V1.0 SP1), SINEMA Server (All versions < V14 SP2), SINUMERIK OPC UA Server (All versions < V2.1), TeleControl Server Basic (All versions < V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication.
A vulnerability has been identified in SINAMICS PERFECT HARMONY GH180 with NXG I control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G21, G22, G23, G26, G28, G31, G32, G38, G43 or G46), SINAMICS PERFECT HARMONY GH180 with NXG II control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G21, G22, G23, G26, G28, G31, G32, G38, G43 or G46). An improperly configured Parameter Read/Write execution via Field bus network may cause the controller to restart. The vulnerability could be exploited by an attacker with network access to the device. Successful exploitation requires no privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in RUGGEDCOM CROSSBOW (All versions < V5.5). The affected systems allow any unauthenticated client to disconnect any active user from the server. An attacker could use this vulnerability to prevent any user to perform actions in the system, causing a denial of service situation.
A vulnerability has been identified in SENTRON 3KC ATC6 Expansion Module Ethernet (3KC9000-8TL75) (All versions). Affected devices expose an unused, unstable http service at port 80/tcp on the Modbus-TCP Ethernet. This could allow an attacker on the same Modbus network to create a denial of service condition that forces the device to reboot.
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems improperly handles memory buffers when parsing X.509 certificates. This could allow an unauthenticated remote attacker to crash the network service.
zipfileUpdate in ext/misc/zipfile.c in SQLite 3.30.1 mishandles a NULL pathname during an update of a ZIP archive.
multiSelect in select.c in SQLite 3.30.1 mishandles certain errors during parsing, as demonstrated by errors from sqlite3WindowRewrite() calls. NOTE: this vulnerability exists because of an incomplete fix for CVE-2019-19880.
libvncclient/sockets.c in LibVNCServer before 0.9.13 has a buffer overflow via a long socket filename.
xmlParseBalancedChunkMemoryRecover in parser.c in libxml2 before 2.9.10 has a memory leak related to newDoc->oldNs.
An issue was discovered in LibVNCServer before 0.9.13. libvncserver/ws_decode.c can lead to a crash because of unaligned accesses in hybiReadAndDecode.
exprListAppendList in window.c in SQLite 3.30.1 allows attackers to trigger an invalid pointer dereference because constant integer values in ORDER BY clauses of window definitions are mishandled.
sqlite3Select in select.c in SQLite 3.30.1 allows a crash if a sub-select uses both DISTINCT and window functions, and also has certain ORDER BY usage.
A vulnerability has been identified in SiNVR/SiVMS Video Server (All versions < V5.0.0), SiNVR/SiVMS Video Server (All versions >= V5.0.0 < V5.0.2). The streaming service (default port 5410/tcp) of the SiVMS/SiNVR Video Server contains a input validation vulnerability, that could allow an unauthenticated remote attacker to cause a Denial-of-Service condition by sending malformed HTTP requests.
A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, KTK ATE530S, SIDOOR ATD430W, SIDOOR ATE530S COATED, SIDOOR ATE531S, SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0), SIMATIC ET 200eco PN, AI 8xRTD/TC, M12-L (6ES7144-6JF00-0BB0), SIMATIC ET 200eco PN, CM 4x IO-Link, M12-L (6ES7148-6JE00-0BB0), SIMATIC ET 200eco PN, CM 8x IO-Link, M12-L (6ES7148-6JG00-0BB0), SIMATIC ET 200eco PN, CM 8x IO-Link, M12-L (6ES7148-6JJ00-0BB0), SIMATIC ET 200eco PN, DI 16x24VDC, M12-L (6ES7141-6BH00-0BB0), SIMATIC ET 200eco PN, DI 8x24VDC, M12-L (6ES7141-6BG00-0BB0), SIMATIC ET 200eco PN, DIQ 16x24VDC/2A, M12-L (6ES7143-6BH00-0BB0), SIMATIC ET 200eco PN, DQ 8x24VDC/0,5A, M12-L (6ES7142-6BG00-0BB0), SIMATIC ET 200eco PN, DQ 8x24VDC/2A, M12-L (6ES7142-6BR00-0BB0), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0), SIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0), SIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0), SIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0), SIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0), SIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants), SIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC MICRO-DRIVE PDC, SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET 200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0), SIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0), SIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0), SIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0), SIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0), SIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0), SIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0), SIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0), SIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0), SIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0), SIMATIC S7-400 H V6 and below CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0), SIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0), SINAMICS S/G Control Unit w. PROFINET, SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0), SIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0), SIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0), SIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0), SIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0), SIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0), SIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0), SIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0). The Interniche-based TCP Stack can be forced to make very expensive calls for every incoming packet which can lead to a denial of service.
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle long file names correctly. This could allow an attacker to create a buffer overflow and create a denial of service condition for the device.
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle HTTP(S) requests to the web server correctly. This could allow an attacker to exhaust system resources and create a denial of service condition for the device.
A vulnerability has been identified in SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V2.5 and < V20.8), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 and < V2.8), SIMATIC S7-1500 Software Controller (All versions >= V2.5 and < V20.8). Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a Denial-of-Service condition. The vulnerability can be triggered if specially crafted UDP packets are sent to the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the device availability.