A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in EcoStruxure Operator Terminal Expert 3.1 Service Pack 1 and prior (formerly known as Vijeo XD)which could cause arbitrary application execution when the computer starts.
A CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exists in Andover Continuum (All versions), which could cause files on the application server filesystem to be viewable when an attacker interferes with an application's processing of XML data.
CWE-287: Improper Authentication vulnerability exists which could cause the execution of commands on the webserver without authentication when sending specially crafted HTTP requests.
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in SFAPV9601 - APC Easy UPS On-Line Software (V2.0 and earlier) when accessing a vulnerable method of `SoundUploadServlet` which may lead to uploading executable files to non-specified directories.
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection'), reflective DLL, vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20), Modicon M580 (all versions prior to V3.10), which, if exploited, could allow attackers to transfer malicious code to the controller.
A CWE-1103: Use of Platform-Dependent Third Party Components with vulnerabilities vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to exploit the component.
**VERSION NOT SUPPORTED WHEN ASSIGNED** A legacy support account in the TriStation software version v4.9.0 and earlier could cause improper access to the TriStation host machine. This was addressed in TriStation version v4.9.1 and v4.10.1 released on May 30, 2013.1
A CWE-89:Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') vulnerability exists in U.motion Servers and Touch Panels (affected versions listed in the security notification) which could cause arbitrary code to be executed when a malicious command is entered.
A CWE-798: Use of Hard-coded Credentials vulnerability exists in the Unity Loader and OS Loader Software (all versions). The fixed credentials are used to simplify file transfer. Today the use of fixed credentials is considered a vulnerability, which could cause unauthorized access to the file transfer service provided by the Modicon PLCs. This could result in various unintended results.
A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists which could allow the attacker to execute malicious code on the Modicon M218, M241, M251, and M258 controllers.
A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.
A CWE-307 Improper Restriction of Excessive Authentication Attempts vulnerability exists in Easergy T300 (Firmware version 1.5.2 and older) which could allow an attacker to gain full access by brute force.
A CWE-330 - Use of Insufficiently Random Values vulnerability exists in Smartlink, PowerTag, and Wiser Series Gateways (see security notification for version information) that could allow unauthorized users to login.
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the transference of malicious code to the controller.
A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T300 (with firmware 2.7 and older) that could cause a wide range of problems, including information exposure, denial of service, and command execution when access to a resource from an attacker is not restricted or incorrectly restricted.
Directory traversal vulnerability in SchneiderWEB on Schneider Electric Modicon PLC Ethernet modules 140CPU65x Exec before 5.5, 140NOC78x Exec before 1.62, 140NOE77x Exec before 6.2, BMXNOC0401 before 2.05, BMXNOE0100 before 2.9, BMXNOE0110x Exec before 6.0, TSXETC101 Exec before 2.04, TSXETY4103x Exec before 5.7, TSXETY5103x Exec before 5.9, TSXP57x ETYPort Exec before 5.7, and TSXP57x Ethernet Copro Exec before 5.5 allows remote attackers to visit arbitrary resources via a crafted HTTP request.
Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors.
A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique such as rainbow tables, effectively disabling the protection that an unpredictable salt would provide.
A CWE-862: Missing Authorization vulnerability exists in Easergy T300 (firmware 2.7 and older), that could cause a wide range of problems, including information exposures, denial of service, and arbitrary code execution when access control checks are not applied consistently.
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause unauthorized command execution when a brute force attack is done over Modbus.
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
Multiple buffer overflows in ActUWzd.dll 1.0.0.1 in Mitsubishi MX Component 3, as distributed in Citect CitectFacilities 7.10 and CitectScada 7.10r1, allow remote attackers to execute arbitrary code via a long string, as demonstrated by a long WzTitle property value to a certain ActiveX control.
The Schneider Electric Magelis XBT HMI controller has a default password for authentication of configuration uploads, which makes it easier for remote attackers to bypass intended access restrictions via crafted configuration data.
Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote attackers to execute arbitrary code by sending TCP port-12397 data that does not comply with a protocol.
A CWE-119: Buffer Errors vulnerability exists in ProClima (all versions prior to version 8.0.0) which allows an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
A CWE-287: Improper Authentication vulnerability exists in the NET55XX Encoder with firmware prior to version 2.1.9.7 which could cause impact to confidentiality, integrity, and availability when a remote attacker crafts a malicious request to the encoder webUI.
A CWE-94: Code Injection vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0.
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
An authentication bypass by capture-replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download.
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
An issue was discovered in Schneider Electric Tableau Server/Desktop Versions 7.0 to 10.1.3 in Wonderware Intelligence Versions 2014R3 and prior. These versions contain a system account that is installed by default. The default system account is difficult to configure with non-default credentials after installation, and changing the default credentials in the embedded Tableau Server is not documented. If Tableau Server is used with Windows integrated security (Active Directory), the software is not vulnerable. However, when Tableau Server is used with local authentication mode, the software is vulnerable. The default system account could be used to gain unauthorized access.
The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port.
The modbus_125_handler function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) allows remote attackers to install arbitrary firmware updates via a MODBUS 125 function code to TCP port 502.
The ComputePassword function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) generates the password for the fwupgrade account by performing a calculation on the MAC address, which makes it easier for remote attackers to obtain access via a (1) ARP request message or (2) Neighbor Solicitation message.
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption.
A CWE-20: Improper Input Validation vulnerability exists in EcoStruxure™ Operator Terminal Expert and Pro-face BLUE (version details in the notification) that could cause arbitrary code execution when the Ethernet Download feature is enable on the HMI.
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.
On Schneider Electric ConneXium Tofino Firewall TCSEFEA23F3F22 before 03.23, TCSEFEA23F3F20/21, and Belden Tofino Xenon Security Appliance, an SSH login can succeed with hardcoded default credentials (if the device is in the uncommissioned state).
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could cause brute force attacks to take over the admin account when the product does not implement a rate limit mechanism on the admin authentication form. Affected Products: Conext™ ComBox (All Versions)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted online data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted setting value messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)
A CWE-190: Integer Overflow or Wraparound vulnerability exists that could cause heap-based buffer overflow, leading to denial of service and potentially remote code execution when an attacker sends multiple specially crafted messages. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)
A Format String: CWE-134 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow an attacker to send a crafted message to the target server, thereby causing arbitrary commands to be executed.
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause modification of an existing file by adding at end of file or create a new file in the context of the Data Server potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause an unauthenticated connection to the UPS when a malformed connection is sent. Affected Product: SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior)
A CWE-269: Improper Privilege Management vulnerability exists that could cause a remote code execution when the transfer command is used over the network.
CWE-200: Information Exposure vulnerability exists that could cause disclosure of credentials when a specially crafted message is sent to the device.