Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key.
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Due to the usage of an outdated cipher mode on port 10005/tcp, an attacker could extract the encryption key from a captured communication with the device.
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). The password used for authentication for the LOGO! Website and the LOGO! Access Tool is sent in a recoverable format. An attacker with access to the network traffic could derive valid logins.
LibVNC commit before d01e1bb4246323ba6fcee3b82ef1faa9b1dac82a contains a memory leak (CWE-655) in VNC server code, which allow an attacker to read stack memory and can be abused for information disclosure. Combined with another vulnerability, it can be used to leak stack memory and bypass ASLR. This attack appear to be exploitable via network connectivity. These vulnerabilities have been fixed in commit d01e1bb4246323ba6fcee3b82ef1faa9b1dac82a.
WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request.
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP8). If configured in an insecure manner, the web server might be susceptible to a directory listing attack.
A vulnerability has been identified in SIMATIC HMI Basic Panels 2nd Generation (incl. SIPLUS variants) (All versions < V16), SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions <= V16), SIMATIC HMI Mobile Panels (All versions <= V16), SIMATIC HMI Unified Comfort Panels (All versions <= V16). Affected devices insufficiently block excessive authentication attempts. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.
A vulnerability has been identified in SIMATIC HMI Unified Comfort Panels (All versions <= V16). Affected devices insufficiently validate authentication attempts as the information given can be truncated to match only a set number of characters versus the whole provided string. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP8). Insecure storage of sensitive information in the configuration files could allow the retrieval of user names.
A vulnerability has been identified in TeleControl Server Basic < V3.1. An attacker with network access to the TeleControl Server Basic's port 8000/tcp could bypass the authentication mechanism and read limited information.
An issue was discovered in LibVNCServer before 0.9.13. There is an information leak (of uninitialized memory contents) in the libvncclient/rfbproto.c ConnectToRFBRepeater function.
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. A directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices.
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V1.81.2). An attacker with network access to the integrated web server on port 80/tcp could obtain the session ID of an active user session. A user must be logged in to the web interface. Siemens recommends to use the integrated webserver on port 80/tcp only in trusted networks.
An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow unauthenticated remote attackers to obtain sensitive device information over the network.
A vulnerability has been identified in Teamcenter Active Workspace V4 (All versions < V4.3.9), Teamcenter Active Workspace V5.0 (All versions < V5.0.7), Teamcenter Active Workspace V5.1 (All versions < V5.1.4). The affected application allows verbose error messages which allow leaking of sensitive information, such as full paths.
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server delivers cookies without the "secure" flag. Modern browsers interpreting the flag would mitigate potential data leakage in case of clear text transmission.
UltraVNC revision 1198 contains multiple memory leaks (CWE-655) in VNC client code, which allow an attacker to read stack memory and can be abused for information disclosure. Combined with another vulnerability, it can be used to leak stack memory and bypass ASLR. This attack appears to be exploitable via network connectivity. These vulnerabilities have been fixed in revision 1199.
UltraVNC revision 1211 contains multiple memory leaks (CWE-665) in VNC server code, which allows an attacker to read stack memory and can be abused for information disclosure. Combined with another vulnerability, it can be used to leak stack memory and bypass ASLR. This attack appears to be exploitable via network connectivity. These vulnerabilities have been fixed in revision 1212.
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). An attacker with network access to affected devices could potentially obtain a TLS session key. If the attacker is able to observe TLS traffic between a legitimate user and the device, then the attacker could decrypt the TLS traffic. The security vulnerability could be exploited by an attacker who has network access to the web interface of the device and who is able to observe TLS traffic between legitimate users and the web interface of the affected device. The vulnerability could impact the confidentiality of the communication between the affected device and a legitimate user. At the time of advisory publication no public exploitation of the security vulnerability was known.
A vulnerability has been identified in Siveillance Video DLNA Server (2019 R1), Siveillance Video DLNA Server (2019 R2), Siveillance Video DLNA Server (2019 R3), Siveillance Video DLNA Server (2020 R1), Siveillance Video DLNA Server (2020 R2), Siveillance Video DLNA Server (2020 R3), Siveillance Video DLNA Server (2021 R1). The affected application contains a path traversal vulnerability that could allow to read arbitrary files on the server that are outside the application’s web document directory. An unauthenticated remote attacker could exploit this issue to access sensitive information for subsequent attacks.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to enumerate valid user names by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to filenames on the server by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The SFTP service (default port 22/tcp) of the Control Center Server (CCS) contains an authentication bypass vulnerability. A remote attacker with network access to the CCS server could exploit this vulnerability to read data from the EDIR directory (for example, the list of all configured stations).
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The Control Center Server (CCS) contains an authentication bypass vulnerability in its XML-based communication protocol as provided by default on ports 5444/tcp and 5440/tcp. A remote attacker with network access to the CCS server could exploit this vulnerability to read the CCS users database, including the passwords of all users in obfuscated cleartext.
A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). A vulnerability in the integrated web server of the affected devices could allow unauthorized attackers to obtain sensitive information about the device, including logs and configurations. At the time of advisory publication no public exploitation of this security vulnerability was known.
If a process running within Aruba Instant crashes, it may leave behind a "core dump", which contains the memory contents of the process at the time it crashed. It was discovered that core dumps are stored in a way that unauthenticated users can access them through the Aruba Instant web interface. Core dumps could contain sensitive information such as keys and passwords. Workaround: Block access to the Aruba Instant web interface from all untrusted users. Resolution: Fixed in Aruba Instant 4.2.4.12, 6.5.4.11, 8.3.0.6, and 8.4.0.0
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. An attacker with network access to the integrated web server (80/tcp and 443/tcp) could bypass the authentication and download sensitive information from the device.
The TRUSTED_SYSTEM_SECURITY function in the SAP RFC Library 6.40 and 7.00 before 20061211 allows remote attackers to verify the existence of users and groups on systems and domains via unspecified vectors, a different vulnerability than CVE-2006-6010. NOTE: This information is based upon a vague initial disclosure. Details will be updated after the grace period has ended.
Aruba Instant 4.x prior to 6.4.4.8-4.2.4.12, 6.5.x prior to 6.5.4.11, 8.3.x prior to 8.3.0.6, and 8.4.x prior to 8.4.0.1 allows Command injection.
A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions < V2.14.1), RUGGEDCOM ROX RX1400 (All versions < V2.14.1), RUGGEDCOM ROX RX1500 (All versions < V2.14.1), RUGGEDCOM ROX RX1501 (All versions < V2.14.1), RUGGEDCOM ROX RX1510 (All versions < V2.14.1), RUGGEDCOM ROX RX1511 (All versions < V2.14.1), RUGGEDCOM ROX RX1512 (All versions < V2.14.1), RUGGEDCOM ROX RX1524 (All versions < V2.14.1), RUGGEDCOM ROX RX1536 (All versions < V2.14.1), RUGGEDCOM ROX RX5000 (All versions < V2.14.1). The affected devices do not properly handle permissions to traverse the file system. If exploited, an attacker could gain access to an overview of the complete file system on the affected devices.
OpenSSH through 7.7 is prone to a user enumeration vulnerability due to not delaying bailout for an invalid authenticating user until after the packet containing the request has been fully parsed, related to auth2-gss.c, auth2-hostbased.c, and auth2-pubkey.c.
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). A directory traversal vulnerability could allow to download arbitrary files from the device. The security vulnerability could be exploited by an attacker with network access to the integrated web server. No user interaction and no authentication is required to exploit the vulnerability. The vulnerability impacts the confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
OpenSSH-portable (OpenSSH) 3.6.1p1 and earlier with PAM support enabled immediately sends an error message when a user does not exist, which allows remote attackers to determine valid usernames via a timing attack.
A vulnerability has been identified in SIMATIC MV540 H (All versions < V3.3), SIMATIC MV540 S (All versions < V3.3), SIMATIC MV550 H (All versions < V3.3), SIMATIC MV550 S (All versions < V3.3), SIMATIC MV560 U (All versions < V3.3), SIMATIC MV560 X (All versions < V3.3). Affected devices do not perform authentication for several web API endpoints. This could allow an unauthenticated remote attacker to read and download data from the device.
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The affected application contains an older feature that allows to import device configurations via a specific endpoint. An attacker could use this vulnerability for information disclosure.
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). Due to improper input validation, the OpenSSL certificate's password could be printed to a file reachable by an attacker.
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). A customized HTTP POST request could force the application to write the status of a given user to a log file, exposing sensitive user information that could provide valuable guidance to an attacker.
Siemens SIMATIC WinCC 7.0 through SP3 and 7.2 allows remote attackers to read arbitrary WinCC station files via crafted packets.
A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions < V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained.
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The Application Server exposes directory listings and files containing sensitive information. This vulnerability is independent from CVE-2019-18287. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC IT Production Suite (All versions < V7.0 SP1 HFX 2), SIMATIC NET PC-Software (All versions < V14), SIMATIC PCS 7 V7.1 (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 V5.X (All versions < V5.5 SP4 HF11), SIMATIC WinCC (TIA Portal) Basic, Comfort, Advanced (All versions < V14), SIMATIC WinCC (TIA Portal) Professional V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) Professional V14 (All versions < V14 SP1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1), SIMATIC WinCC V7.0 SP2 and earlier versions (All versions < V7.0 SP2 Upd 12), SIMATIC WinCC V7.0 SP3 (All versions < V7.0 SP3 Upd 8), SIMATIC WinCC V7.2 (All versions < V7.2 Upd 14), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 11), SIMATIC WinCC V7.4 (All versions < V7.4 SP1), SIMIT V9.0 (All versions < V9.0 SP1), SINEMA Remote Connect Client (All versions < V1.0 SP3), SINEMA Server (All versions < V13 SP2), SOFTNET Security Client V5.0 (All versions), Security Configuration Tool (SCT) (All versions < V4.3 HF1), TeleControl Server Basic (All versions < V3.0 SP2), WinAC RTX 2010 SP2 (All versions), WinAC RTX F 2010 SP2 (All versions). Unquoted service paths could allow local Microsoft Windows operating system users to escalate their privileges if the affected products are not installed under their default path ("C:\Program Files\*" or the localized equivalent).
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with local access to the MS3000 Server and a low privileged user account could gain root privileges by manipulating specific files in the local file system. This vulnerability is independent from CVE-2019-18308. Please note that an attacker needs to have local access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V2.0 SP1). Some pages that should only be accessible by a privileged user can also be accessed by a non-privileged user. The security vulnerability could be exploited by an attacker with network access and valid credentials for the web interface. No user interaction is required. The vulnerability could allow an attacker to access information that he should not be able to read. The affected information does not include passwords. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in PCS neo (Administration Console) (All versions < V3.1), TIA Portal (V15, V15.1 and V16). Manipulating certain files in specific folders could allow a local attacker to execute code with SYSTEM privileges. The security vulnerability could be exploited by an attacker with a valid account and limited access rights on the system.
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions), CP-8021 MASTER MODULE (All versions), CP-8022 MASTER MODULE WITH GPRS (All versions). The component allows to activate a web server module which provides unauthenticated access to its web pages. This could allow an attacker to retrieve debug-level information from the component such as internal network topology or connected systems.
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP-8022 MASTER MODULE WITH GPRS (All versions < V16.20). The web server of the affected system allows access to logfiles and diagnostic data generated by a privileged user. An unauthenticated attacker could access the files by knowing the corresponding download links.
A vulnerability has been identified in SIMATIC CN 4100 (All versions < V4.0.1). The affected device contains a USB port which allows unauthenticated connections. This could allow an attacker with physical access to the device to trigger reboot that could cause denial of service condition.
A vulnerability has been identified in SIMATIC MV400 family (All Versions < V7.0.6). An authenticated attacker could escalate privileges by sending specially crafted requests to the integrated webserver. The security vulnerability can be exploited by an attacker with network access to the device. Valid user credentials, but no user interaction are required. Successful exploitation compromises integrity and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in Climatix POL909 (AWB module) (All versions < V11.44), Climatix POL909 (AWM module) (All versions < V11.36). The handling of log files in the web application of affected devices contains an information disclosure vulnerability which could allow logged in users to access sensitive files.
A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) V15 (All versions), SIMATIC STEP 7 (TIA Portal) V16 (All versions < V16 Update 5), SIMATIC STEP 7 (TIA Portal) V17 (All versions < V17 Update 2). An attacker could achieve privilege escalation on the web server of certain devices due to improper access control vulnerability in the engineering system software. The attacker needs to have direct access to the impacted web server.